Documentation page: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/583237633/VT11+Relay+output
Product page: https://vutlan.com/digital-output/72-vt11-relay-contact-5a.html
Function and purpose
Relay switchable contact. Can be used together with equipment, for example for switching it ON/OFF. For controlling devices that have dry contact input or controlling their power source. Can manage 5A power for magnetic locks, bolt locks, solenoid electromagnets, sirens, light sources, heaters, air conditioners, etc.
Can be connected to any Vutlan unit with 12V relay outputs.
Technical specifications
VT590 | |
---|---|
Dimensions | 60×18×18 mm |
Weight | 60 g |
Input | wire terminal 3.81mm 2P |
Outputs | wire terminal 5.0mm 2P |
Operating temperature | Temperature: Min. -50 °C - Max.105 °C |
Operating humidity | Humidity : Min. 5% - Max. 95% (Non-Condensing) |
Mounting | The mounting bracket, sticker, and screws are included. |
Power consumption | 12 mW |
Max. distance m | 200 m |
HS Code | 9025 11 800 |
Components | Manufactured in E.U. |
Special features | Can be connected to any monitoring system or device with 12V outputs. |
Max. switching voltage | 250VAC / 30VDC |
Max switching current | 5A |
Max. switching power | 1250VA / 150W |
Min. contact load | No gold plated: 5VDC 10mA |
LED indication
The sensor has a red LED indicator that sticks from the top cover
Normal | Reverse | |
---|---|---|
contact is closed | Red | - |
contact is open | - | Red |
Drawings
Connecting switchable contact
Switchable contact can only be connected to 12V 0.25A outputs of the Vutlan monitoring system. The diagram below explains how to connect two VT11 switchable contacts to the monitoring system.
Usage examples with installation diagram
Example 1. Using "VT11 / dry contact output" to control a device with dry contact input.
Example 2. Control siren, light source, heater.
Example 3. Control magnetic lock, electric motor, solenoid electromagnet
Cable pinouts
Switchable contact uses a standard two-wire cable for connecting to the monitoring unit.