Function and purpose

High-quality pressure, humidity, and temperature sensor with a reliable price.

Technical specifications


Communications
Description
Sensor typeCAN digital sensor
Inputs/Outputsx2 RJ11 6P4C ports
Daisy chainYes, a daisy chain is possible for all CAN sensors.
Max. distance from the monitoring unit:225m
LED indicators:Red / Green (RUN/ERROR)
Accuracy


Pressure RMS noise:0.2Pa (equivalent to 1.7cm)
Pressure error:±0.25% (equivalent to 1m at 400m height change)
Pressure from °C:±1.5Pa/K (equivalent to ±12.6cm at 1 °C temperature change)
RH accuracy:± 3% RH (max)
Hysteresis:≤2% RH
Response time1 s
Temperature: 1.5°C
Environmental
Pressure range:300 to 1100 hPa
Working temperature range:−40 to +85 °С
Humidity operating range:0 to 95% RH
Power Requirement
Power input:12V DC, 1A (power supplied on a CAN bus chain)
Current consumption:1 Watt
Mechanics
Dimensions:68x47x26 mm
Packaging weight:160 g
Mounting options:Desktop, Wall mount
General
Manufactured in:Slovak Republic, European Union
Manufactured by:Vutlan s.r.o.
HS code:9025 11 800
Warranty:90 days

Physical description



 

1. LEDs: "RUN" (green) - indicates that the appliance is correctly connected to the main module, "ERROR or ERR" (red) - indicates an error, the appliance lost connection to the main module.

2. "Pressure, humidity & temperature sensor" - The sensor is located outside of the enclosure for better measurement and precision.

3. "TR" - This switch should be turned to "ON" (down) position if the sensor is the last one in the CAN chain. Otherwise, the switch should be turned to "OFF" (up) position.

Example 1: We have 1 CAN sensor connected to the main module VT8101 on the CAN bus. In this case, this sensor is the only one and the last one in the CAN chain, and its 2nd "TR" switch should be in the "ON" (down) position.

Example 2: We have 5 sensors or modules connected to the main module via the CAN bus. The sensor is not the last sensor in a chain, for example, it is located in the middle of the chain. In this case, the "TR" switch must be in the "OFF" (up) position.

Example 2: We have 5 sensors or modules connected to the main module via the CAN bus. The sensor is  the last sensor in a chain. The "TR" switch must be in the "ON(down) position.

4. "CAN" - two equivalent digital connectors RJ11 6P4C for the connection to the master module, CAN sensors, or CAN extensions on a CAN bus, with auto-sensing.

Packaging includes

Include Page
VT450 package content
VT450 package content

Drawings

Example connection

Connecting CAN devices

Include Page
CAN devices connection
CAN devices connection

CAN configuration

Include Page
Setting up CAN
Setting up CAN

API: managing system elements by 3rd party Software

Vutlan has an open API. Read more at:

https://vutlan.atlassian.net/wiki/spaces/API/pages/335740995/Managing+system+elements