Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Documentation link: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/1834680385/VT103+Alarm+beacon

...

Usage

Needed for light and sound alarms. Has The cable length is 1.5 m in lengthmeters. Connects to 12V DC, 0.25A electronic relay output of Vutlan monitoring systems.

...

Package includes

Include Page
VT103 package content
VT103 package content

...

Drawings

...

View file
nameVT103_strobe_siren.pdf

...

Installation drawing

View file
nameVT103_strobe_siren_installation.pdf

...

Connecting 12V devices to Vutlan monitoring systems

Include Page
Connecting 12V devices to 12V outputs
Connecting 12V devices to 12V outputs

12V relay configuration (alarm beacon or strobe light)

...

b) To configure the relay: go to System tree >> Power 12V 0.25A >> Choose relayImage Removed

...

c) By default Power-1 and Power-2. Rename it, set the initial state, and set Pulse duration time in seconds to a specific period.Image Removed

...

Additionally: 12V relay configuration

Include Page
12V 0.25A relay configuration
12V 0.25A relay configuration

Cable pinouts

Strobe The strobe light uses a standard two-wire cable for connecting to the monitoring unit.Image Removed

...

Technical specifications

VT105

Dimensions

Size 70 x 36 x 56 mm, cable 3m

Weight

150g

Cable length

3m

Output

Light and sound

Rated voltage

12V DC, 1A

Power consumption

250mA

Sound pressure

108 dB

Tone frequency

3.8 kHz

Flash frequency

2.5Hz red 150/min

Mounting

Wall mount

HS code

8531 10 300

Case, color

ABS plastic, red, white

IP rating standard

IP54

Operating temperature

Temperature: Min. -50 °C - Max.105 °C

Operating humidity

Humidity : Min. 5% - Max. 95% (Non-Condensing)

Components

Manufactured in E.U.

...

Copyright of:

Vutlan s.r.o. (LLC)

Remote Infrastructure Monitoring and Control

43 ul.Svornosti, 821 06 Bratislava,

Slovak RepublicRepublic