Image Modified  End of Life: 31.10.2022

Image Modified

Physical description


Info

It is possible to connect up to two readers to one Vutlan monitoring system. Please use a splitter to do this. In such a case both readers are seen by the system as one reader. This is useful when one reader is used for entrance and one reader for the exit of the same door.


When "VT10" is installed inside of monitoring unit, "VT10" looks like this:

Image Modified

1a. RJ9 jack for connecting 1-Wire sensors.

1b. Green LED. If the green light is "ON", then the 1-Wire board is on. There's an element inside the monitoring unit's interface that can be switched "ON" and "OFF", which activates the 1-Wire bus.

Technical specifications

Feature
Description
Product dimensionsLength 44mm, Width 23mm, Height 15mm
Inputs terminalsRJ9 4P4C
Network Interface1-Wire
Status Indicators1-Wire status LED
Operating temperatureTemperature: Min. -10° C - Max.+80° C
Other1- Wire sensors are plug-&-playVT10 needs to be activated (On/Off) inside the interface.
Packing size(Length, Width, Height) 45x45x120 mm
Manufactured in (country)Manufactured in Slovak Republic, E.U.


Connection

Monitoring units have the option of installing a "VT10 / 1-Wire board" (expansion board). The board is mounted and connected inside the monitoring unit. 1-Wire technology is based on a serial communication protocol that uses one data line and a reference ground between the master (for example, the VT335 / Monitoring Unit) and one wire slave.

Installation and connecting of VT10 1-Wire board

Note

To install and connect extension units: switch off the appliance, unplug from the outlet or disconnect the power connector. 


1


Image Modified


Carefully unscrew screws holding the cover and open it.

Note

Depending on the monitoring system, it may have 1-Wire, Antenna, GSM, or Dry Contacts, or any other additional modules installed inside. Carefully open the box by unplugging, if necessary, any cables that connect from the top cover to the bottom cover.


2


Image Modified


Break 2 steel bridges in the 1-Wire hole of the appliance case (e.g. VT335 top metal)cover. Using forceps (cutter) with thin nozzles cut the thin bridges in the hole. Make sure that no burrs are left.


3


Image Modified


Set up the 1-Wire board on 2 steel spacing sleeves inside the appliance case (e.g. VT335 top metal cover), attach the board with two M3 screws from supply to the sleeves.
4

Image Modified

Image Modified

Connect "16 wire IDC16 flat cable" supplied with a "1-Wire extension" board to the connector on the 1-Wire board and the mainboard (e.g. VT335 board).

Make sure is installed in 2-3 position



6


Image Modified


Close and fasten the cover. Carefully place the top cover back so that all cover wings fit in and all cutoff points match the panel holes.

Activating 1-Wire interface:

After the "VT10 / 1-Wire board" has been installed inside the system, You need to check if the 1-Wire interface is On.

Include Page
Setting up 1-Wire
Setting up 1-Wire

Connecting 1-Wire sensors:

All 1-Wire sensors are Plug&Play. Use the following examples for instructions on how to connect sensors:

Example 1:

Image Modified


Example 2:

Image Modified

Package includes:

Include Page
VT10 / 1-Wire Board (Inventory)
VT10 / 1-Wire Board (Inventory)

Accessories:

The following accessories can be used with the 1-Wire interface. Accessories are ordered separately.

TCS15 RJ11prolongation cable