Physical description

Image Removed   Image RemovedDocumentation page: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/1834713171/VT500+Temperature+sensor+v2

Product page: https://vutlan.com/can-sensors/25-vt430-rack-control.html

Image AddedImage Added

Function

The unit has all possibilities for rack control, PIR sensor for door control, 2 dry contacts, temperature and humidity sensors.

Physical description

   Image Added


1. "TR" - is the nearest switch to CAN inputs. This switch should be turned "ON" on the last sensor in the CAN chain. The last sensor in the long chain with the a length of more than 10 meters, terminator should be in "OFF" position.

...

Note

Do not use DIP switch "FR", it should always be OFF. If this switched switch is turned ON, the module will turn off. This switch is only needed for programming purposes!

2. "CAN" - two equivalent digital connectors RJ12 for the connection of CAN sensors and CAN extensions on a CAN bus, with auto-sensing.

3. "1, 2" - Dry contacts contact inputs terminals, can be used for access control.

4. "Sensor" - Temperature and humidity sensor

5. "LEDs" - LEDs: "RUN" - indicates appliance connection status to the main module, "ERR" - indicates appliance lost connection to the main module.

56"PIR" - Door IR access sensor. Use white sticker supplied to control the door open/closed.


Technical specifications

Feature
Description
Type / Network interfaceCAN digital sensor
UsageIR, humidity, and temperature sensor; x2 dry contact inputs (digital inputs);
Product dimensions(Width, Height, Depth) 89 x 27.1 x 48.2 mm
Packing weight270 g
Power supplyPower is supplied over the CAN bus
Power ConsumptionPower Consumption
Operating temperature

Optimal temperature range:  -10° C to +80° C

Extended temperature range:  -40° С to +100° C

Mounting possibilities

Desktop

Indoor

Rack-mountable

Wall mount

Max. distance from the unit225 m
Measured Humidity0 ... 95% RH
Humidity accuracy3%
Measured Temperature-10 … +85 °С
Temperature accuracy1 °С
IR sensor distanceminimum 1 cm., maximum 3-4 cm.
Inputs terminals

Dry contacts / Digital inputs: x2 contacts (pitch 3,5mm, type IN)

RJ-12 ports: x2

Status IndicatorsRed / Green Led
Manufactured in (country)Manufactured in Slovak Republic, E.U.
HS Code8471 50 000
Daisy chainYes, possible using CAN bus


Installation

There is a mounting bracket on the unit. Fix unit by M5 or M6 bolts on the cabinet or the rack profile in front of the door. Glue the white sticker on the door in front of the unit IR sensor. Connect CAN input of the unit by RJ11/RJ12 cable supplied to the CAN input of previous CAN unit or monitoring system. The red LED lights up. Match the TR bus terminators on the attached CAN units. CAN bus terminators TR (position 2 in VT450) should be in the ON state only at the end CAN units port and in Off states (1,2) for all intermediate units. One CAN bus can have not more than 8 CAN units, sensors, and/or another CAN device. 

If necessary, connect dry contacts, door sensors, or triggers to the unit.

Image Added


Connection

To connect CAN unit to the system, open interface and go  CAN Configuration  Select tab CAN.

...

If the survey is reset after click clicking "Configure", it means that the line is not connected (bad cable and/or bad connectors) or not matched terminators on the bus. It is necessary to check and change the status of the line or the TR terminations.

Image Modified

pic.1.1: FR is OFF, TR is ON.                    pic.1.2: FR is OFF, TR is OFF.(Developer notes: physical description picture: case v.2)

CAN devices connection

Include Page
CAN devices connection
CAN devices connection

Setting up CAN

Include Page
Setting up CAN
Setting up CAN

Drawings

Image Added

Image Added


...