Physical description
Documentation page: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/1834713171/VT500+Temperature+sensor+v2
Product page: https://vutlan.com/can-sensors/25-vt430-rack-control.html
Function
The unit has all possibilities for rack control, PIR sensor for door control, 2 dry contacts, temperature and humidity sensors.
Physical description
1. "TR" - is the nearest switch to CAN inputs. This switch should be turned "ON" on the last sensor in the CAN chain. The last sensor in the long chain with the a length of more than 10 meters, terminator should be in "OFF" position.
...
Note |
---|
Do not use DIP switch "FR", it should always be OFF. If this switched switch is turned ON, the module will turn off. This switch is only needed for programming purposes! |
2. "CAN" - two equivalent digital connectors RJ12 for the connection of CAN sensors and CAN extensions on a CAN bus, with auto-sensing.
3. "1, 2" - Dry contacts contact inputs terminals, can be used for access control.
4. "Sensor" - Temperature and humidity sensor
5. "LEDs" - LEDs: "RUN" - indicates appliance connection status to the main module, "ERR" - indicates appliance lost connection to the main module.
56. "PIR" - Door IR access sensor. Use white sticker supplied to control the door open/closed.
Technical specifications
Feature | Description |
---|---|
Type / Network interface | CAN digital sensor |
Usage | IR, humidity, and temperature sensor; x2 dry contact inputs (digital inputs); |
Product dimensions | (Width, Height, Depth) 89 x 27.1 x 48.2 mm |
Packing weight | 270 g |
Power supply | Power is supplied over the CAN bus |
Power Consumption | Power Consumption |
Operating temperature | Optimal temperature range: -10° C to +80° C Extended temperature range: -40° С to +100° C |
Mounting possibilities | Desktop Indoor Rack-mountable Wall mount |
Max. distance from the unit | 225 m |
Measured Humidity | 0 ... 95% RH |
Humidity accuracy | 3% |
Measured Temperature | -10 … +85 °С |
Temperature accuracy | 1 °С |
IR sensor distance | minimum 1 cm., maximum 3-4 cm. |
Inputs terminals | Dry contacts / Digital inputs: x2 contacts (pitch 3,5mm, type IN) RJ-12 ports: x2 |
Status Indicators | Red / Green Led |
Manufactured in (country) | Manufactured in Slovak Republic, E.U. |
HS Code | 8471 50 000 |
Daisy chain | Yes, possible using CAN bus |
Installation
There is a mounting bracket on the unit. Fix unit by M5 or M6 bolts on the cabinet or the rack profile in front of the door. Glue the white sticker on the door in front of the unit IR sensor. Connect CAN input of the unit by RJ11/RJ12 cable supplied to the CAN input of previous CAN unit or monitoring system. The red LED lights up. Match the TR bus terminators on the attached CAN units. CAN bus terminators TR (position 2 in VT450) should be in the ON state only at the end CAN units port and in Off states (1,2) for all intermediate units. One CAN bus can have not more than 8 CAN units, sensors, and/or another CAN device.
If necessary, connect dry contacts, door sensors, or triggers to the unit.
Connection
To connect CAN unit to the system, open interface and go
CAN Configuration Select tab CAN....
If the survey is reset after click clicking "Configure", it means that the line is not connected (bad cable and/or bad connectors) or not matched terminators on the bus. It is necessary to check and change the status of the line or the TR terminations.
pic.1.1: FR is OFF, TR is ON. pic.1.2: FR is OFF, TR is OFF.(Developer notes: physical description picture: case v.2)
CAN devices connection
Include Page | ||||
---|---|---|---|---|
|
Setting up CAN
Include Page | ||||
---|---|---|---|---|
|