Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 15 Next »

Product page: https://www.vutlan.com/accessories/40-vt105-strobe.html

Documentation link: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/1834680385/VT103+Alarm+beacon

Function and purpose

VT103 is needed for light and sound alarms.

Connects to 12V DC, 0.25A electronic relay output of Vutlan monitoring systems. Can be configured to sound/light an alarm if an alarm event has been triggered.

Can be used with 3rd party controllers.

Technical specifications

Function & Purpose

Description

Device type:

12V DC sound and light alarm

Rated voltage

12V DC, 1A

Sound pressure

108 dB

Tone frequency

3.8 kHz

Flash frequency

2.5Hz red 150/min

Output

Light and sound

Envrironmental

Description

Operating temperature

Temperature: Min. -50 °C - Max.105 °C

Operating humidity

Humidity : Min. 5% - Max. 95% (Non-Condensing)

IP rating standard

IP54

Power

Description

Power consumption

250mA

Mechanical

Description

Weight

150g

Dimensions

Size 70 x 36 x 56 mm, cable 3m

Mounting

Wall mount

Cable length

3 meters

Case color

ABS plastic, red, white

General

Description

Manufactrued in

Manufactured in E.U.

HS code

8531 10 300

GTIN

8588009886594

Warranty

Package includes

Package includes:

Package content

Description

Quantity

1

Alarm beacon with 1.5m cable

1 pc

2

4J-S sticky clamps

2 pcs

3

2.5mm Dowels

2 pcs

4

Screws for dowels, B2.9*20

2 pcs

Drawings

Connecting 12V devices to Vutlan monitoring systems

Page linked https://vutlan.atlassian.net/wiki/spaces/DEN/pages/71181064/Connecting+12V+devices+to+12V+outputs

12V relay configuration (alarm beacon or strobe light)

a) Login to the web interface of the monitoring system

b) To configure the relay: go to System tree >> Power 12V 0.25A >> Choose relay

c) By default Power-1 and Power-2. Rename it, set the initial state, and set Pulse duration time in seconds to a specific period.

Configuration for 12V outputs

Page linked https://vutlan.atlassian.net/wiki/spaces/DEN/pages/601030668/12V+0.25A+relay+configuration

Cable pinouts

The strobe light uses a standard two-wire cable for connecting to the monitoring unit.


Copyright of:

Vutlan s.r.o. (LLC)

Remote Infrastructure Monitoring and Control

43 ul.Svornosti, 821 06 Bratislava,

Slovak Republic

  • No labels