Function and purpose

For installation at the bottom of IT racks and cabinets; at the bottom of raised floors; at the bottom of trays and under equipment that can potentially leak. When water is in contact with the metal cores, the sensor indicates the emergence of moisture.
Attention! Metal cores are detectors of water, mount strictly downwards as close as its possible to a floor.

Package includes

Package content can be found at : VT590 package content

Connecting leak sensor

Sensor uses standard Vutlan analog sensor cable for connecting to the monitoring unit. You can find further instructions at: Analog sensors connection

Installation using a sticker and a bracket

1) There's a round bump at the bottom of the plastic enclosure of the sensor. It is used for fastening when the sensor is mounted together with the on walls using a screw. In current example it is not needed. If you are planning to mount a device defferently, do not follow this step.

Cut the round bump using a knife so that the bottom of plastic enclosure will be flat.


2) a) Stick the mounting bracket to the bottom surface.

    b) Stick a sensor to the mounting bracket following the rule from next paragraph.


3) If  Depending on the surface where the sensor will be installed follow either A or B. If the surface is conductive, then the electric loop between left and right metal bars sticking out the sensor will be closed, which means there's water which connects two bars.

A) If the surface is not conductive. Then mount the sensor metal bars as close to the surface as possible.

B) If the the surface is conductive. Then mount the sensor metal bars a bit further from the surface but not too far, so that the detection of water would be possible.


4) The sensor is mounted.

Installation examples

Please find installation examples in our article "Water leakage detection using cable sensor and spot sensor".

Cable pinouts

Sensor uses standard Vutlan analog sensor cable for connecting to the monitoring unit. You can find further instructions at: Analog sensors connection

Technical specifications

VT590
Dimensions60×18×18 mm
Weight125 g
Input

RJ-12 / RJ-11

OutputsRJ11 / RJ12 (6p4c)
Operating temperatureTemperature : Min. -10 °C - Max.80 °C
Operating humidityHumidity : Min. 5% - Max. 95% (Non-Condensing)
MountingMounting bracket included. Installed at the bottom of racks or floors or trays.
Power consumption60mW
Max. distance m100 m
HS Code9025 80 400
ComponentsManufactured in E.U.
Special featuresCable 2 m.