Function and purpose


For installation at the bottom of IT racks and cabinets; at the bottom of raised floors; at the bottom of trays and under equipment that can potentially leak. When water is in contact with the metal cores, the sensor indicates the emergence of moisture.
Attention! Metal cores are detectors of water, mount strictly downwards as close as its possible to a floor.

Package includes

Package content can be found at : VT591 & WDC package content

Connecting WDC / Water detection rope

  1. Connect WDC rope sensor to the VT591 leak sensor.
  2. Wire the WDC rope around or under potentially leaking objects around the perimeter or under raised floors.
  3. Cconnect the sensor to the monitoring unit. Connection is plug-an-play.
  4. Sensor is ready to use.

Connecting WLC / Water leak cable

  1. Connect the "VT591 / Water leak sensor" to the monitoring unit. Connection is plug-an-play.
  2. Connect "VTC / Terminal cable" to VT591 sensor.
  3. Connect "WLC / Water detection cable" to "VTC / Terminal cable".
  4. Connect any additional "WLC / Water detection cables" to each other as shown on picture above to make a chain connection.
  5. Wire the WLC rope around or under potentially leaking objects around the perimeter or under raised floors.
  6. Put a protective cap on the connector of the last WLC cable in a chain.
  7. Sensor is ready to use.

Installation examples

Please find installation examples in our article "Water leakage detection using cable sensor and spot sensor".

Cable pinouts

Sensor uses standard Vutlan analog sensor cable(RJ11/RJ12 to RJ11/RJ12) for connecting to the monitoring unit. You can find further instructions at: Analog sensors connection

Technical specifications

VT591 / Water leak sensor specifications
Dimensions60×18×18 mm
Weight60 g
Input

2 wire (WDC cable)

OutputRJ11 / RJ12 (6p4c)
Operating temperatureTemperature : Min. -10 °C - Max.80 °C
Operating humidityHumidity : Min. 5% - Max. 95% (Non-Condensing)
MountingMounting bracket included.
Power consumption60mW
Max. distance m100 m
HS Code9025 80 400
ComponentsManufactured in E.U.
Special featuresResponse time: 15 sec., Recovery time: Depends on how fast the sensor dries out

WDC / Water detection rope specifications

DescriptionWDC can detect moisture (works until the dew point) and does not welcome pollution!
Detectable liquidsClean, polluted & distilled water; acids; alkalis; alcohols and other electrically conductive liquid
Diameter3 mm diameter
Lengths

Order options include 6m, 10m, 17m, 25m, 50m or custom length.

Weight

15 g/m

Operating temperatureMin. -50° C, Max. 105° C
Max. rope length225 m
Conductor27% Ni

WLC / Water leak cable specifications

DescriptionWLC can work in high humidity, pollution and hazardous waste
Detectable liquidsClean, polluted & distilled water; acids; alkalis; alcohols and other electrically conductive liquid
Diameter5.5 mm diameter
Lengths

Order options include 10m, 15m, 25m, 50m or custom length.

Weight

26 g/m

Operating humidity0° - 100 %
Max. cable length225 m
Inputsx2 wires