Function and purpose

For installation at the bottom of IT racks and cabinets; at the bottom of raised floors; at the bottom of trays and under equipment that can potentially leak. When water is in contact with the metal cores, the sensor indicates the emergence of moisture.
Attention! Metal cores are detectors of water, mount strictly downwards as close as its possible to a floor.

Package includes

Package content can be found at : VT591 & WDC package content

Connecting leak sensor

  1. Connect WDC rope sensor to the VT591 leak sensor.
  2. Wire the WDC rope around or under potentially leaking objects around the perimeter or under raised floors.
  3. Cconnect the sensor to the monitoring unit. Connection is plug-an-play.
  4. Sensor is ready to use.

Installation examples

Please find installation examples in our article "Water leakage detection using cable sensor and spot sensor".

Cable pinouts

Sensor uses standard Vutlan analog sensor cable for connecting to the monitoring unit. You can find further instructions at: Analog sensors connection

Technical specifications

VT591
Dimensions60×18×18 mm
Weight60 g
Input

2 wire (WDC cable)

OutputRJ11 / RJ12 (6p4c)
Operating temperatureTemperature : Min. -10 °C - Max.80 °C
Operating humidityHumidity : Min. 5% - Max. 95% (Non-Condensing)
MountingMounting bracket included.
Power consumption60mW
Max. distance m100 m
HS Code9025 80 400
ComponentsManufactured in E.U.
Special featuresResponse time: 15 sec., Recovery time: Depends on how fast the sensor dries out