Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

Image Modified

...

  End of Life:

...

  30.09.2023

Documentation page: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/93421575/VT590+Leak+sensor

Product page: https://vutlan.com/analog-sensors/22-vt590-spot-water-detector.html

...

Function and purpose

For the installation at the bottom of IT racks and cabinets; at the bottom of raised floors; at the bottom of trays and under equipment that can potentially leak. When water is in contact with both metal cores, the sensor indicates the emergence of moisture.
Attention! Metal cores are detectors of water, mount strictly downwards as close as possible to a floor.

Technical specifications

Communications

Description

Sensor type:

Analog sensor

Outputs:

x1 RJ11 6P4C port

Daisy chain?

No

Max. distance from the monitoring unit:

100 m

Environmental


Operating temperature:

Min. -10 °C - Max.80 °C

Operating humidity:

5 to 95% (Non-Condensing)

Power requirements


Power consumption

60mW

Mechanics


Dimensions:

60×18×18 mm

Pin diameter

4mm ⌀

Pin length

From pin top to enclosure: approximately 8.4mm

Mounting:

Mounting bracket included. Installed at the bottom of racks or floors or trays.

Packaging weight:

125 g

Cable length:

3m

General


Manufactured in:

Slovak Republic, European Union

Manufactured by:

Vutlan s.r.o.

HS Code:

9025 80 400

Warranty:

90 days

Package includes

Include Page
VT590 package content (legacy)
VT590 package content (legacy)

Drawings

View file
nameVT590_tray_mounting.pdf

...

View file
nameVT590_leak_sensor.pdf

...

Connecting the leak sensor

The sensor uses a standard Vutlan analog sensor cable for connecting to the monitoring unit. You can find further instructions at: in Analog sensors connectionImage Removed

...

Installation using a sticker and a bracket

1) There's a round bump at the bottom of the plastic enclosure of the sensor. It is used for fastening when the sensor is mounted on walls using a screw. In the current example, it is not needed. If you are planning to mount a device differently, do not follow this step.

Cut the round bump using a knife so that the bottom of a plastic enclosure will be flat.Image Removed

...


2) a) Stick the mounting bracket to the bottom surface.

    b) Stick a sensor to the mounting bracket following the rule from the next paragraph.Image Removed

...


3) If  Depending on the surface where the sensor will be installed follow either A or B. If the surface is conductive, then the electric loop between the left and right metal bars sticking out of the sensor will be closed, which means there's water that connects the two bars.

...

B) If the surface is conductive. Then mount the sensor metal bars a bit further from the surface but not too far, so that the detection of water would be possible.Image Removed

...


4) The sensor is mounted.Image Removed

...

Installation examples

Please find installation examples in our article "Water leakage detection using cable sensor and spot sensor".

...

Connecting analog sensors

The sensor uses a standard Vutlan analog sensor cable for connecting to the monitoring unit.

Include Page
Analog sensors connection
Analog sensors connection

Configure analog sensors

Include Page
Sensor configuration
Sensor configuration

API: managing system elements by 3rd party Software

Vutlan has an open API. Read more at:

Application programming interface (API) (EN) v.2: https://vutlan.atlassian.net/wiki/spaces/API/pages/335904791/Application+programming+interface+API+EN+v.2

Analog sensors API: https://vutlan.atlassian.net/wiki/spaces/API/pages/335806556/Analog+sensors


Copyright:

Vutlan s.r.o. (LLC)

Remote Infrastructure Monitoring and Control

43 ul.Svornosti, 821 06 Bratislava,

Slovak Republic