Physical description

"RS-485 to USB adapter" is used for connecting Modbus RTU devices/meters/sensors to Vutlan VT900 and VT960 monitoring units.

Connection

Image RemovedImage RemovedImage RemovedImage RemovedImage RemovedPlease read article Connecting Modbus devices first.

Example 1: Using "RS485 to USB adapter" with internal termination.

  • Sensors are connected in a daisy chain connection.
  • 120Ω resistor is used at the end of the chain.
  • Twisted pair cable is used for A(+) and B(-).
  • "RS-485 to USB adapter" has an internal termination and it is switched ON.
  • The data is transferred to Vutlan monitoring unit using USB port.
  • Up to 31 devices can be used.
  • Overall cable length no more than 1000 meters.

Image Added

Example 2: Using "RS485 to USB adapter" withiout internal termination.

  • The same as the first example with the exception that the "RS-485 to USB adapter" does not have a built in termination.
  • T ermination (120Ω resistor) is added at the start of the chain.

Image Added


Activating Modbus interface:

After "VT85 / Modbus extension board" and all of the Modbus devices have been connected to it, you need to activate it and configure: Creating virtual Modbus RTU element




Developer notes: