Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

  1. Change the type of the sensor by choosing "Current". Choosing any type of sensor does not affect sensor properties, it only changes the sensor icon for the comfort of usage.



  2. Change the name of the sensor, for example, "AC current".

  3. How to use an "Expression formula": 20 * (x-B).  "B" indicates the voltage at the output of the current transducer at zero current. 

    1. Image RemovedImage Added
  4. To measure "B", measure the readings of the monitoring system at zero current in the transducer. Typically B is about 0.017 - 0.021.

    Image RemovedImage Added

    Then you can write the formula "20*(x-B)". Push OK.

    Image RemovedImage Added
  5. Now the system is ready to measure the current in the transducer core.

  6. Finally put in the threshold levels by dragging: Low alarm, Low warning, High warning, High alarm levels.


    For example, the graph above shows that the state of the sensor at the moment is "Normal" because 20.4 is between "Low warning" and "High warning" states, which is considered a "normal" state.

  7. Click “Save” on a diskette at the bottom right of the “Properties” window. The page will reload and the sensor will update by changing its icon type to

    (abbreviation from "Ampers").

...

Warning

Do not tweak the transducer's variable resistors. They are tweaked by the manufacturer for optimal measurement. Tweaking these may result in incorrect measurements.

Technical specifications

HAT-100Q1 / AC current transducer

Dimensions

Size 60 × 61 × 16 mm

Weight

150 g

Measured AC current

0-100A

Operating temperature

Temperature: Min. -10° C - Max.80° C

Operating humidity

Min. 5% - Max. 95% (Non-Condensing)

Power input

-12V / +12V

Outputs

4 pin terminal

Mounting

Wall mount

Power Consumption

1 Watt

Max. distance m

50 m

HS Code

9030 33 100


VT407 / AC current converter

Type of sensor

Analog sensor

Dimensions

Size 68 × 47 x 26 mm

Weight

160 g

Inputs

RJ-12 / RJ-11

Operating temperature

Min. -10° C - Max.80° C

Operating humidity

Min. 5% - Max. 95% (Non-Condensing)

Power input

12V DC, 1A

Mounting

Desktop, Wall mount

Power Consumption

100 mW

Components

Manufactured in the E.U.

Max. distance m

50 m

Special Features

Transferred voltage - 0 .. 5V

HS Code

9030 33 100

Example 1: Equipment life prediction using a current sensor

...

Frequently asked questions

Question

Answer

Can I connect more than 1 set of "VT407+HAT-100Q1"?

Yes, you can. VT407 is an analog sensor. The sensor can be connected to any Analog port of Vutlan monitoring systems. It also can be connected to VT408 / Extension unit