Product page: https://vutlan.com/analog-sensors/171-vt572-radar-motion-sensor.html
Function and purpose
A high-performance sensor/detector using microwave radar as a control signal source to detect objects or human movement. This product is an indoor energy-saving high-sensitivity detector.
...
The maximum amount of sensors connected to the Vutlan monitoring unit and maximum length can be extended using the "VT408 / Sensor extension unit" or “VT408DIN / Extension unit”.
...
The sensor can be connected to available analog ports of the system. See the picture below.
The sensor can be connected to the “VT408 / Extension unit”. See the picture below.
The sensor can be connected to the “VT408DIN / Extension unit”. See the picture below.
...
Technical specifications
General parameters | Description |
Type: | Analog sensor |
Usage: | Motion, movement, position, proximity detector/sensor |
Technology: | Doppler Principle (transmit and receive signals) using microwave radar with minituarized planar antennas |
Daisy chain connection: | Not possible |
HS Code: | 8531 80 950 |
Manufactured in (country): | Manufactured in Slovak Republic, E.U. |
Certification standards: | FCC/CE/SRRC/RoHS |
LEDs: | Red when movement detected. Green when no movement. |
RF parameters | Description/value |
Frequency Range: | 5.725GHz-5.875GHz |
Transmit Power: | -4dBm |
Antenna: | Built-in flat antennas |
Hardware parameters | Description/value |
Operating Temperature: | Sensor PCB board: from -20 ℃ to +85 ℃ ABS plastic enclosure: from -20 ℃ to +80 °C PVC RJ cable: from -15 ℃ to +80 °C |
Storage temperature: | from -40° С to +100° C |
Operating humidity: | Sensor PCB board: 0 to 85% |
Storage humidity: | 0 to 95 % |
Power Consumption: | 100 mW |
Installation | |
Installation height: | 3 meters is recommended |
Detection angle: | 120° degrees |
Sensing distance: | maximum is 12 meters |
Inducting distance: | Radius About 5-6m |
Max. Induction Radius: | The radius is 6 meters when hanging height is 3 meters |
Cable length: | 2 meters |
Mounting possibilities: | Wall or ceiling mount |
Output terminal: | RJ-11 / 6P4C |
Max. distance from the unit: | 100 meters from Vutlan controller or from “VT408 / extension unit” or from “VT408DIN / DIN extension unit” |
Induction range
The graphs below are showing the distance in meters. The darker area in the figures below shows where the sensor’s sensitivity is high, while the light area has low sensitivity.
...