Documentation page: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/1904279553/CAN-12V-1A+CAN+Power+Supply

Product page: https://vutlan.com/can-sensors/150-CAN12V1A.html

...

Function and purpose

Increases The additional power supply is needed only if the number of CAN sensors connected to in a CAN bus chain is more than 12 sensors. Supplies power for a maximum of 15 additional sensors. Needed only if the number of sensors in a CAN bus chain is greater than each additional group of 12 sensors.

Technical specifications

Communications
Description

Type

Power supply for CAN bus chain

Input

RJ11 6P4C CAN port

⌀3.4/1,35 mm 12V

Output

RJ11 6P4C CAN port

Daisy chain

Allows daisy chain

Max. qty of  CAN sensors powered:

15

LED indicators:

Green (Status On/Off)

Environmental

Working temperature range:

 −40 °C to +100 °C

Humidity operating range:

0-95% RH

Power Requirement

Power input:

12V DC, min. 1A, max.2A

Mechanics

Dimensions:

68 x 67 x 26,2 mm (LxWxH)

Packaging weight:

190 g

Mounting options:

Desktop, Wall mount, Indoor

General

Manufactured in:

Slovak Republic, European Union

Manufactured by:

Vutlan s.r.o.

HS code:

8504 40 90

Warranty:

90 days

Physical description

...

1. "Power 12V DC" - power input.

...

  • Plug CAN-12V-1A into the power supply socket using a Euro schuko Schuko power adapter. The status LED should light GREEN.

  • Plug all additional sensors (group 2) into the "OUTPUT" port of the CAN-12V-1A power supply unit. Group 2 should have no more than 15 sensors connected in a chain.

  • All sensors should light ON. If some of the sensors do not switch ON, decrease the number of sensors connected to CAN-12V-1A, and check the status of each sensor again. If successful, continue to the next step.

...

  • Connect GROUP1's last sensor to the INPUT port of the CAN-12V-1A module.

  • Switch the last sensor's TR button to the OFF position in GROUP1. Switch the last sensor's TR button to the ON position in GROUP2.

  • You can now CONFIGURE the CAN bus in the web interface. See the "CAN Configuration" step below.

...