Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

The maximum amount of connected VT407 converters and the maximum length from the monitoring unit can be extended using the VT408 / Sensor extension unit.

Components

The transducer HAT-100Q1 consists of a plastic housing with an open/closed AC current loop and 4 4-pin terminal connectors. The current converter VT407 is a simple plastic case with 4 pins input, DC 12V socket, and RJ output for connection to monitoring units.

...

HAT-100Q1 / AC current transducer

Function & purpose

Description

Sensor type:

AC current transducer

Used for:

Measures AC currents in the range of 0-100A and and send the data in the range 0-5V

Measured AC current:

0-100A

Communications

Description

Maxamum distance:

50 meters from the monitoring unit or VT408 extension unit

Outputs:

4 pin terminal, pitch 3.81mm

Environmental

Description

Operating temperature:

Temperature: Min. -10° C - Max. 80° C

Operating humidity:

Min. 5% - Max. 95% (Non-Condensing)

Power

Description

Power input:

±12V

Mecanical & Packaging

Description

Weight:

150 g

Dimensions:

Size 60 × 61 × 16 mm, internal diameter 21mm

Mounting:

Wall mount, hanging

Geeral

Description

Manufactured in:

China

HS Code:

9030 33 100

GTIN:

8588009886549

Warranty:

90 days

...

VT407 / AC current converter

Function & purpose

Decription

Type of sensor:

Converter/adapter for AC current transducer

USed Used for:

Captures the data from AC current transducer and transfers the data to the Vutlan monitoring unit as an analog signal.

Communications

Decription

Output:

RJ-11 / RJ-12 6P4C

Transferred voltage

- 0 .. 5V

Max. distance m

50 metersInputs:

4P terminal, pitch 5.08mm:

GND, 0…+5V, -12V, +12V

Maximum distance:

50 meters from the monitoring unit or VT408 analog sensor extension

Environmental

Dexription

Operating temperature:

Min. -10° C - Max. 80° C

Operating humidity:

Min. 5% - Max. 95% (Non-Condensing)

Power

Decription

Power input:

12V DC, 1A

Power Consumptionconsumption:

100 mW

Mechanical & Packaging

Decription

Weight:

160 g

Dimensions:

Size 68 × 47 x 26 mm

Mounting:

Desktop, Wall mount

General

Decription

Manufactured in:

Manufactured in the EU, Slovak Republic, Vutlan s.r.o.

HS Code:

9030 33 100

GTIN:

8588009886556

Safety instructions

...

Example 3: Switch off equipment before it overloads

...

Package content VT407

Page linked https://vutlan.atlassian.net/wiki/spaces/DEN/pages/89554954/VT407+package+contents

Include Page
VT407 package contents
VT407 package contents

Package content HAT-100Q1

Page linked https://vutlan.atlassian.net/wiki/spaces/DEN/pages/89653249/HAT-100Q1+package+content

Include Page
HAT-100Q1 package content
HAT-100Q1 package content

Frequently asked questions

Question

Answer

Can I connect more than 1 set of "VT407+HAT-100Q1"?

Yes, you can. VT407 is an analog sensor. The sensor can be connected to any Analog port of Vutlan monitoring systems. It also can be connected to VT408 / Extension unit .


...

Copyright: