VT335x, VT336x, VT825x, VT855x, VT960x are the monitoring units and can not connect. For scalability please use extension units and embedded boards.
...
● Built-in □ None ♦ Extension possible ◊ Not extendable
Versions | VT960 | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Device Management: Web, SNMP | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Sensor access: Three-level by login | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Interface | VT960 | ||||||||||
LAN: Ethernet 10/100 Mbit | Yes | Yes | Yes | Yes | Yes2 x 1 Gbit | 100 Mbit | 100 Mbit | 100 Mbit | 100 Mbit | 100 Mbit | |
OS: Linux | v.6.2 | v.6.2 | v.6.2 | v.6.2 | v.6.2 | ||||||
Interface: Any browser | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Memory RAM: | 2 Gb | 128 Mb | 128 Mb | 128 Mb | 128 Mb | 128 Mb | |||||
CPU speed: | 1.8 GHz | 1 GHz | 720 MHz | 720 MHz | 720 MHz | 600 MHz | |||||
Total CPU cores: | 8 | 2 | 2 | 2 | 2 | 2 | |||||
Clock: Built-in clock | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Timer: Built-in watchdog | Yes | Yes | Yes | Yes | Yes | Yes | |||||
The maximum amount of sensors: physical sensors, dry contacts, relays | 500 | 150 | 130 | 100 | 100 | 100 | |||||
The maximum amount of elements: notifications, triggers, timers, logic, sensors, dry contacts, SNMP Get, SNMP Trap, Dial task, and other elements | 3000 | 1000 | 1000 | 700 | 700 | 700 | |||||
Networking / Protocol support | VT960 | ||||||||||
LTE Gateway mode: Internet access (routing for internal network) (modem ordered separately) | Yes | Yes | Yes | Yes | NoYes | - | |||||
LTE Access mode: Internet access over LTE (modem ordered separately) | Yes | Yes | Yes | Yes | Yes | No- | |||||
Network protocols: DHCP; HTTP; HTTPS; SNMP v1, v2c, v3; SMTP; FTP; Syslog; TLS; | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Modbus RTU | Using extension VT485m | Using extension VT485m | Using extension VT485m | Using extension VT485m | NoUsing extension VT485m | - | |||||
RS485 / OSDPv2: reader access control | Yes | Yes | Yes | Yes | NoUsing extension VT485R | Using extension VT485R | Using extension VT485R | Using extension VT485R | - | ||
Modbus TCP / IP | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Static routing | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Dynamic DynDNS | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Access via RADIUS server | Yes | Yes | Yes | Yes | Yes | Yes | |||||
VPN: secure data communications; secure change of connection between LTE and LAN | Yes | Yes | Yes | Yes | Yes | No- | |||||
SSL installation | Yes | Yes | Yes | Yes | Yes | Yes | |||||
NTP server | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Alerts / Notifications | VT960 | ||||||||||
Alert types: E-mail, FTP log, Syslog, SMTP, SNMP Traps, SMS (Modem is ordered separately), Web-to-SMS, | Yes | Yes | Yes | Yes | Yes | Yes | |||||
A maximum number of "mail to" recipients in an E-mail notification: | 20 | 20 | 20 | 20 | 20 | 20 | |||||
A maximum number of "SMS to" recipients in an SMS notification: also the maximum amount of phone numbers | 20 | 20 | 20 | 20 | 20 | - | |||||
Virtual sensors | VT960 | ||||||||||
Pings: Built-in function for server pinging. Test the reachability of a host in a network. | Yes | Yes | Yes | Yes | Yes | Yes | |||||
IP cameras: Connect the IP MJPEG camera with a proxy via the master module. Only view, no record. | 4 | 4 | 4 | 4 | 4 | 4 | |||||
Get SNMP: Read data from external equipment via SNMP PDU GET (v1/2c) | Yes | Yes | Yes | Yes | Yes | Yes | |||||
User keys: Add users who have access using an RFID reader. | Yes | Yes | Yes | Yes | Yes | No- | |||||
Logic schemes: Used to specify automatic actions to events that occur in the system. | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Timers: Allows you to plan the events in the system. | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Triggers: Generate events in the system if logic is triggered. | Yes | Yes | Yes | Yes | Yes | Yes | |||||
SNMP traps | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Virtual Math element (combine several sensor data and calculate new data) | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Logic schemes | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Modbus TCP/IP: read/write | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Power | VT960 | ||||||||||
Energy efficiency: (EU Energy level) | Grad C | Grad A | Grad A | Grad A | Grad A | Grad A | |||||
Power input (230V AC): | x2 inputs option | x2 inputs option | x2 inputs option | No-No | - | No- | |||||
Power input (24 ÷ 48V DC): | x2 inputs option | x2 inputs option | No | No | Nox2 inputs option | Yes | - | - | |||
Power input (12V DC): | - | x1 input option | x1 input option | x2 inputsx2 inputs | Input | Input | |||||
Fuse: Fuse at the inlet | 1 A | 1 A | 1 A | PTC | PTC | PTC | |||||
Min. power consumption: | 5 W | 1 W | 1 W | 1 W | 1 W | 1 W | |||||
Max. power consumption: | 25 W | 10 W | 10 W | 10 W | 10 W | 6 W | |||||
The maximum current load on the relay: | 10А | 10А | 10А | 250mА | 250mА | 250mА | |||||
Redundant power supply: built-in voltage monitor, voltage range 9-12.6V. | Yes AC/DC DC/DC | Yes AC/DC DC/DC | Yes AC/DC DC/DC | Yes DC/DC | Yes DC 12V | - | |||||
Outputs | VT960 | ||||||||||
Relay outputs: latching relays 240V*10A | 2 | 2 | 2 | - | - | - | |||||
Relays outputs: 12V 0.25A | 2 | 2 | 2 | 2 | 2 | 2 | |||||
Max. dry contact outputs (contact closures/digital outputs) | 2 | 8 | - | 5 | - | - | |||||
Inputs | VT960 | ||||||||||
Analog port: 6P6C for connection of an analog sensor. (extendable using CAN bus) | 8 built-in ports, extended using extension unit | 8 built-in ports, extended using extension unit | 8 built-in ports, extended using extension unit | 4 built-in ports, extended using extension unit | 4 built-in ports, extended using extension unit | 4 built-in ports, extended using extension unit | |||||
CAN port: Max number of sensors Use CAN-12V-1A for connecting more than 12 devices. | x2 port, x32 devices in total | x2 port, x32 devices in total | x1 port, max. 32 devices | x1 port, max. 32 devices | x1 port, max. 32 devices | x1 port, max. 10 devices | |||||
Dry contact inputs: (contact closures/digital inputs) | 48 | 32 | 16 | 8 | 4 | 2 | |||||
Modbus RTU (RS-485): Max. line length 1000m | Using extension VT485m | Using extension VT485m | Using extension VT485m | Using extension VT485m | Using extension VT485m | - | |||||
OSDP v2 reader extension: | Yes | Using extension VT485R | Using extension VT485R | Using extension VT485R | Using extension VT485R | - | |||||
Video | VT960 | ||||||||||
USB cameras | x11 | 1 | x11x1 | 1 | x11x1 | 1 | |||||
IP cameras | x4 | x4 | x4 | x4 | x4 | x4 | |||||
RTSP IP camera | 2 | - | - | - | - | - | |||||
Other connectors | VT960 | ||||||||||
Ethernet port: 10/100Mbit | - | x11x1 | 1 | x11x1 | 1 | x11 | |||||
Ethernet port: 10/100/1000Mit | 2 | - | - | - | - | - | |||||
USB 2.0 Type A | 2 | - | - | - | - | - | |||||
x1 USB 2.0 micro | x1 | x1 | x1 | x1 | Type C | 1 | 1 | 1 | 1 | 1 | 1 |
Switch Normal / Recovery: returns the device to factory settings | Yes | Yes | Yes | Yes | Yes | Yes | |||||
External Memory / Logs | VT960 | ||||||||||
Micro SD memory card slot (SDXC up to 512 Gb) | Yes | Yes | Yes | Yes | Yes | Yes | |||||
SD card formatting function (FAT32) | Yes | Yes | Yes | Yes | Yes | Yes | |||||
USB flash drive: logs, sensor readings, item settings, etc. | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Send system log to e-mail: Logs, sensor data, elements settings, etc. | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Sensor dump files: save the per-second samples of analog and discrete sensors | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Yes | Yes | Yes | Yes | Yes | Yes | ||||||
Send to FTP server: Logs, sensor data, elements settings, etc. | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Maximum amount of log files: 10,000 logs/days = 27 years | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Sample rate/period (logs, graphs) | 1 s | 1 s | 1 s | 1 s | 1 s | 1 s | |||||
Reservation of settings | VT960 | ||||||||||
“i” series (e.g. VT335i): System settings are compatible | Yes | Yes | Yes | Yes | Yes | ||||||
Modem (extension ordered separately) | VT960 | ||||||||||
4G LTE modem: ordered separately. | VT7672 | - | |||||||||
Modem modes:
| Gateway / Access / SMS | Gateway / Access / SMS | Gateway / Access / SMS | Gateway / Access / SMS | Gateway / Access / SMS | - | |||||
Modem LED: STATUS | Yes | Yes | Yes | Yes | Yes | - | |||||
Embedded onboard sensors | VT960 | ||||||||||
Temperature sensor: +/- 1 °C PCB temperature. | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Power supply voltage sensor: Accuracy (1%) | Main & Reserve | Main & Reserve | Main & Reserve | Main & Reserve | Main & Reserve | Yes | |||||
LED indication | VT960 | ||||||||||
Ethernet LAN: LINK | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Ethernet LAN: ACT | Yes | Yes | Yes | Yes | Yes | Yes | |||||
CAN bus: STATUS | Yes | Yes | Yes | Yes | Yes | Yes | |||||
System: STATUS (ACT) | Yes | Yes | Yes | Yes | Yes | Yes | |||||
System: ERROR (ERR) | Yes | Yes | Yes | Yes | Yes | Yes | |||||
System: ALARM | Yes | Yes | Yes | Yes | Yes | Yes | |||||
12V 0.25A outputs: STATUS (e.g. E1, E2) | x2 | x2 | x2 | x2 | x2 | x2 | |||||
MODBUS RTU: STATUS | VT485M | VT485M | VT485M | VT485M | VT485M | - | |||||
ODSP Reader. | Yes | VT485R | VT485R | VT485R | VT485R | - | |||||
NC/NO/COM Relay (e.g. R1, R2) | x2 | x2 | x2 | - | - | - | |||||
Environmental characteristics | VT960 | ||||||||||
Operating temperature: -10 to 80 70 °C | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Storage temperature: –25 to 85 °C | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Operating humidity: 0 to 90 %, non-condensing | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Storage humidity: 0 to 95 %, non-condensing | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Other Features | VT960 | ||||||||||
Installation: | 19” 1U | 19” 1U | 19” 1U | DIN rail, Wall | Desktop | Desktop | |||||
Casing: | Sheet metal | Sheet metal | Plastic | Sheet metal | Plastic | ||||||
Dimensions (L x W x H) in mm: | 440x44x90 | 440x44x90 | L_212.5 H_90.1 D_32.20 | 180x35x80 | 150x29x100 | ||||||
Weight: | 1,6 kg | 1,5 kg | 0,7 kg | 0,5 kg | |||||||
External chassis grounding: M4 thread | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Web interface (panels) | VT960 | ||||||||||
Dashboard panel: | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Overall statistics panel: | Yes | Yes | Yes | Yes | Yes | Yes | |||||
System tree panel: sensors and devices displayed in a hierarchy | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Dry outputs panel: | Yes | Yes | Yes | Yes | No | Yes | |||||
Dry inputs panel: | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Event log panel: amount of logs | Yes | 300 | 300 | Yes | 300 | 200 | |||||
Logic schemes panel: | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Cameras panel: | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Map panel: 5 layers | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Users panel: | Yes | Yes | Yes | Yes | Yes | Yes | |||||
CAN configuration panel: | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Graphs panel: | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Reset smoke detectors panel: | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Preferences panel: Web GUI, Network, Time, Logging, DynDNS, SNMP, RADIUS, FTP backup, VPN Clent, Modbus RTU, GPS, SMTP, Routing | Yes | Yes | Yes | Yes | Yes | Yes | |||||
System menu panel: About, Firmware, Export, Support | Yes | Yes | Yes | Yes | Yes | Yes | |||||
List of latest sent SMS messages: | 200 | 200 | 200 | Yes200 | 150 | 200 | |||||
Analog sensor power reset: resets smoke sensors | Yes | Yes | Yes | Yes | Yes | Yes |
● Built-in □ None ♦ Extension possible ◊ Not extendable