Datasheet page: https://vutlan.atlassian.net/l/cp/aJLea5p1

Product page: https://vutlan.com/can-sensors/27-vt460-smoke-humidity-and-temperature-sensor.html

...

Physical description

...

From the picture above:

  1. Temperature & humidity sensor

  2. CAN bus ports

  3. Pinheads (3 pins)

  4. LED (More info in the "LEDs section" in the article: CAN devices connection)

Info

The sensor can not be used on its own. It must be used together with Vutlan monitoring systems.

Installation procedure

Notes on assembly

...

Depending on the version of VT460, please choose the below picture to help you accomplish that.

Case

Diagram

Description

1

Image Modified

Older VT460 sensors use a pin head jumper.

a) For all sensors except the last sensor in the chain put "pinhead jumper" on pins: 2 and 3. TR is OFF.

b) For the last sensor in the chain put "pinhead jumper" on pins: 1 and 2. TR is ON.

Case

2

Image Modified

Newer VT460 sensors use a slide switch.

a) For all sensors except the last sensor in the chain switch the slide switch UP to turn up. TR is OFF.

b) For the last sensor in the chain switch the slide switch to the BOTTOM/DOWN. TR is ON.

Connecting CAN sensors

Include Page
CAN devices connection
CAN devices connection

...

During system operation, take a needle or paper clip and insert it into the hole on the cover of the sensor, try to move it there until the blinking dimly LED will flash flashes brightly. That means that the sensor is in a good state. After inspection, return the sensor /s to a normal state. To do this, either disconnect them from the system, or in a system interface, go to the smoke sensors tab, and restart them.

...

Avoid high-frequency noise and the impact of dust on the sensor, the noise and dust cause false alarms.

Technical specifications

VT460

Dimensions

Ø100×45 mm

Weight

290 g

Inputs

2 x RJ-12

Operating temperature

Min. -10° C, Max.80° C

Operating humidity

Min. 5% - Max. 95% (Non-Condensing)

Power consumption

100 mW

Status Indicators

Red LED

Max. distance m

225 m

HS Code

8531 10 950

Components

Manufactured in E.U.

Special Features

Daisy chain

Mounting

On the сeiling

Safety instructions

  • Please observe the valid regulations for installation in the country in which the smoke alarm is installed and operated , and the national regulations for accident prevention. Please also observe any internal company regulations, such as work, operating, and safety regulations.

  • The technical specifications and limit values stated must not be exceeded under any circumstances. In particular, this applies to the specified ambient temperature range and IP protection category.

  • If a higher IP protection category is required for a special application, the smoke alarm must be installed in an appropriate housing or an appropriate enclosure with the required IP protection category.

...