Functional description & components

...

Image Added

...

Image Added

...

Function & Order options

DC monitor is used for the measurement of DC voltage and converting data into the format of the IP monitoring system. The system interface allows you to assign the sensor and introduce the function data conversion.

VT410

...

5V: measured voltage 0-

...

5V

VT410 15V: measured voltage 0-15V

VT410 75V: measured voltage 0-75V, the better measurement for low voltages.

Info

The sensor can not be used on its own. It must be used together with Vutlan monitoring systems.

...

Inventory

...

Drawing

...

Installation

Warning

Only a 6P6C RJ12 cable can be used with the sensor! The cable is included with the sensor.

1. Connect one end of the shielded 6P6C RJ12 cable to any Vutlan monitoring unit's analog port A1-A8 and the other end to the VT410 / DC Voltage Monitor.Image Removed

...

2. Connect "+" and "-" to the 2P terminal.

3. Insert the terminal into VT410.

Image Removed

...

Example 1 : measurement of battery voltage

...

Example 2: measurement of 48V electric circuit

...

Configuration

 Once VT410 was connected to the analog ports of the Vutlan monitoring system, the monitoring system will automatically sense the current transducer as a sensor. It will appear in: "System tree" >> "Autodetect" >> (abbreviation from : Voltage function, used for sensor monitors and converters)Image Removed

...

Click on the sensor to open its properties. A modal window with sensor properties will pop up.Image Removed

...

1. Change the name of the sensor, for example, "DC Voltage monitor 1".

...

3. Use "Expression formula": Each sensor has its own expression formula. It is printed on the case of the sensor. For example:Image Removed

...

This current sensor has an expression formula equal to "14.993*(x-0.019)

...

5. Click “Save” or “Apply” at the bottom of the “Properties” window. The page will reload. Save settings to flash by pressing on

Technical specifications

VT410 75V / DC Voltage monitor

Dimensions

Size 60 × 18 × 18 mm

Measured voltage

0-75 V

Weight

100 g

Operating temperature

Temperature: Min. -10° C - Max.80° C

Operating humidity

Min. 5% - Max. 95% (Non-Condensing)

Outputs

4 pin terminal

Mounting

Desktop, Wall mount

Power Consumption

100 mW

K coefficient

=~14.8, used inside the interface

Max. distance m

50 m

HS Code

9030 33 100

Special features

Isolation - 1 kV, Measured voltage - 0..60 V, Accuracy - 1%.

VT410 14.4V / DC Voltage monitor

Dimensions

Size 60 × 18 × 18 mm

Measured voltage

0-14.4 V

Weight

100 g

Operating temperature

Temperature: Min. -10° C - Max.80° C

Operating humidity

Min. 5% - Max. 95% (Non-Condensing)

Outputs

4 pin terminal

Mounting

Desktop, Wall mount

Power Consumption

100 mW

K coefficient

=~ ?, used inside the interface

Max. distance m

50 m

HS Code

9030 33 100

Special features

Isolation - 1 kV, Measured voltage - 0..60 V, Accuracy - 1%.