Function and purpose

Info

Notice on 6th June 2019: The product has been altered. RJ9 4P2C connected is now used instead of 2P Power Terminal.


Sensor must be used together with

Image Modified

WLC / Water leak cable

(recommended)

(ordered separately)

or

Image Modified

WDC / Water detection rope

(ordered separately)

When water is in contact with detection cable sensor indicates the emergence of moisture. "WDC / Water detection rope" and "WLC / Water leakage cable" are ordered separately! The whole area can be effectively monitored by placing the cable near or along possible flood sources.

Dimensions


Usage examples

Image AddedImage AddedImage Added

Technical specifications


VT591 / Water leak sensor specifications
Dimensions60×18×18 mm
Weight60 g
Input

2 wire (WDC cable)

OutputRJ11 / RJ12 (6p4c)
Operating temperatureTemperature : Min. -10 °C - Max.80 °C
Operating humidityHumidity : Min. 5% - Max. 95% (Non-Condensing)
MountingMounting bracket included.
Power consumption60mW
Max. distance m100 m
HS Code9025 80 400
ComponentsManufactured in E.U.
Special featuresResponse time: 15 sec., Recovery time: Depends on how fast the sensor dries out


WDC / Water detection rope specifications

DescriptionWDC can detect moisture (works until the dew point) and does not welcome pollution!
Detectable liquidsClean, polluted & distilled water; acids; alkalis; alcohols and other electrically conductive liquid
Diameter3 mm diameter
Lengths

Order options include 6m, 10m, 17m, 25m, 50m or custom length.

Weight

15 g/m

Operating temperatureMin. -50° C, Max. 105° C
Max. rope length225 m
Conductor27% Ni


WLC / Water leak cable specifications

DescriptionWLC can work in high humidity, pollution and hazardous waste
Detectable liquidsClean, polluted & distilled water; acids; alkalis; alcohols and other electrically conductive liquid
Diameter5.5 mm diameter
Lengths

Order options include 10m, 15m, 25m, 50m or custom length.

Weight

26 g/m

Operating humidity0° - 100 %
Max. cable length225 m
Inputsx2 wires


Include Page
VT591, WDC, WLC package content
VT591, WDC, WLC package content

Mounting


Connecting WDC / Water detection rope

Image Added

  1. Connect WDC rope sensor to the VT591 leak sensor.
  2. Wire the WDC rope around or under potentially leaking objects around the perimeter or under raised floors.
  3. Cconnect the sensor to the monitoring unit. Connection is plug-an-play.
  4. Sensor is ready to use.

Connecting WLC / Water leak cable

Image Added

  1. Connect the "VT591 / Water leak sensor" to the monitoring unit. Connection is plug-an-play.
  2. Connect "VTC / Terminal cable" to VT591 sensor.
  3. Connect "WLC / Water detection cable" to "VTC / Terminal cable".
  4. Connect any additional "WLC / Water detection cables" to each other as shown on picture above to make a chain connection.
  5. Wire the WLC rope around or under potentially leaking objects around the perimeter or under raised floors.
  6. Put a protective cap on the connector of the last WLC cable in a chain.
  7. Sensor is ready to use.

Include Page
Analog sensors connection
Analog sensors connection

Installation examples

Please find installation examples in our article "Water leakage detection using cable sensor and spot sensor".

...

Sensor uses standard Vutlan analog sensor cable(RJ11/RJ12 to RJ11/RJ12) for connecting to the monitoring unit. You can find further instructions at: Analog sensors connection


Technical support

The device does not contain any user-serviceable parts. If the power meter requires service, contact your local sales representative. Do not open the device. Opening the device voids the warranty.

Troubleshooting

The following table describes potential problems and their possible causes. It also describes checks you can perform or possible solutions for each. After referring to this table, if you cannot resolve the problem, contact the your local Vutlan sales representative for assistance.


Potential ProblemPossible CausePossible Solution
The data being displayed is inaccurate or not what you expect.

Incorrect setup values.Check that You use the correct f(x) formula
Incorrect voltage inputs.Check power meter voltage input terminals to verify that adequate voltage is present
Power meter is wired improperly.Check that all wires are connected correctly and that they are energized. See “Wiring Diagrams” of the device.
Sensor does not appear in Vutlan monitoring interfaceCommunications lines are improperly connected.Check 6P4C RJ11 communication cable.
Communication cable is inserted in to a wrong port.6P4C RJ11 communication cable must be inserted into analog port of Vutlan monitoring system.