Function and purpose
For installation at the bottom of IT racks and cabinets; at the bottom of raised floors; at the bottom of trays and under equipment that can potentially leak. When water is in contact with the metal cores, the sensor indicates the emergence of moisture.
Attention! Metal cores are detectors of water, mount strictly downwards as close as its possible to a floor.
Package includes
Package content can be found at : VT591 & WDC package content
Connecting WDC / Water detection rope
- Connect WDC rope sensor to the VT591 leak sensor.
- Wire the WDC rope around or under potentially leaking objects around the perimeter or under raised floors.
- Cconnect the sensor to the monitoring unit. Connection is plug-an-play.
- Sensor is ready to use.
Connecting WLC / Water leak cable
- Connect the "VT591 / Water leak sensor" to the monitoring unit. Connection is plug-an-play.
- Connect "VTC / Terminal cable" to VT591 sensor.
- Connect "WLC / Water detection cable" to "VTC / Terminal cable".
- Connect any additional "WLC / Water detection cables" to each other as shown on picture above to make a chain connection.
- Wire the WLC rope around or under potentially leaking objects around the perimeter or under raised floors.
- Put a protective cap on the connector of the last WLC cable in a chain.
- Sensor is ready to use.
Installation examples
Please find installation examples in our article "Water leakage detection using cable sensor and spot sensor".
Cable pinouts
Sensor uses standard Vutlan analog sensor cable(RJ11/RJ12 to RJ11/RJ12) for connecting to the monitoring unit. You can find further instructions at: Analog sensors connection
Sensor must be used together with
(recommended) (ordered separately) |
---|
or
(ordered separately) |
---|
When water is in contact with detection cable sensor indicates the emergence of moisture. "WDC / Water detection rope" and "WLC / Water leakage cable" are ordered separately! The whole area can be effectively monitored by placing the cable near or along possible flood sources.
Technical specifications
VT591 / Water leak sensor specifications | |
---|---|
Dimensions | 60×18×18 mm |
Weight | 60 g |
Input | 2 wire (WDC cable) |
Output | RJ11 / RJ12 (6p4c) |
Operating temperature | Temperature : Min. -10 °C - Max.80 °C |
Operating humidity | Humidity : Min. 5% - Max. 95% (Non-Condensing) |
Mounting | Mounting bracket included. |
Power consumption | 60mW |
Max. distance m | 100 m |
HS Code | 9025 80 400 |
Components | Manufactured in E.U. |
Special features | Response time: 15 sec., Recovery time: Depends on how fast the sensor dries out |
...
WLC / Water leak cable specifications | |
---|---|
Description | WLC can work in high humidity, pollution and hazardous waste |
Detectable liquids | Clean, polluted & distilled water; acids; alkalis; alcohols and other electrically conductive liquid |
Diameter | 5.5 mm diameter |
Lengths | Order options include 10m, 15m, 25m, 50m or custom length. |
Weight | 26 g/m |
Operating humidity | 0° - 100 % |
Max. cable length | 225 m |
Inputs | x2 wires |
Include Page | ||||
---|---|---|---|---|
|
Connecting WDC / Water detection rope
- Connect WDC rope sensor to the VT591 leak sensor.
- Wire the WDC rope around or under potentially leaking objects around the perimeter or under raised floors.
- Cconnect the sensor to the monitoring unit. Connection is plug-an-play.
- Sensor is ready to use.
Connecting WLC / Water leak cable
- Connect the "VT591 / Water leak sensor" to the monitoring unit. Connection is plug-an-play.
- Connect "VTC / Terminal cable" to VT591 sensor.
- Connect "WLC / Water detection cable" to "VTC / Terminal cable".
- Connect any additional "WLC / Water detection cables" to each other as shown on picture above to make a chain connection.
- Wire the WLC rope around or under potentially leaking objects around the perimeter or under raised floors.
- Put a protective cap on the connector of the last WLC cable in a chain.
- Sensor is ready to use.
Installation examples
Please find installation examples in our article "Water leakage detection using cable sensor and spot sensor".
Cable pinouts
Sensor uses standard Vutlan analog sensor cable(RJ11/RJ12 to RJ11/RJ12) for connecting to the monitoring unit. You can find further instructions at: Analog sensors connection