Functional description & components

Image Added

Image Added


Physical description VT416

Image Added

Function

Simple Bidirectional DC current monitor VT416 can measure DC currents in range of ± 8A ± 6A

Components

The monitor consists of a plastic housing with two inputs, one with Hall DC current sensor with 4 pins terminal connector and second RJ9 for connection to monitoring system. 

Image Added

Safety instructions

  • Please observe the valid regulations for installation in the country in which current monitor is installed and operated, and the national regulations for accident prevention. Please also observe any internal company regulations, such as work, operating and safety regulations.
  • The technical specifications and limit values stated must not be exceeded under any circumstances. In particular, this applies to the specified ambient temperature range and IP protection category.

...

To ensure proper functionality, the conditions specified in section “Technical specifications” must be observed.

Installation procedure

Image Added

Notes on assembly

  • Be careful, sensor max. voltage for isolation is 2kV.
  • The monitor can measure DC current on any current wire, not more then 3 mm in diameter. 
  • Max. distance for DC current transducer  from monitoring unit is 50 meters.

...

  • Mount current monitor using self-adhesive feet or stickers.  
  • Connect current wires to terminals.

...

  1. Change type of the sensor by choosing "Current". Choosing any type of the sensor does not affect sensor properties, it only changes sensor icon for comfort of usage.



  2. Change the name of sensor, for example "Current".
  3. Use "Expression formula", for VT416 if initial current I=0 then output V=~2.5V, that means B= ~-2.5; full scale is 5V, 8A=5V and -8A=0V, that means K=3.25. Expr= 3.25*(x-2.5). Please calculate "B" accurate with zero current.
  4. Put in the threshold levels by dragging: Low alarm, Low warning, High warning, High alarm levels.

    For example, graph above shows that the state of the sensor at the moment is "Normal" because 20.4 is between "Low warning" and "High warning" states, which is considered "Normal" state.
  5. Click “Save” or “Apply” at the bottom of the “Properties” window. The page will reload and the sensor will update by changing it's icon type to (abreviation from: "Ampers").

Mounting

a) Wall mounting can be achieved by using stickers supplied in the package.

Image Added

b) Or you can use adhesive legs for putting it on a surface.

Image Added

Technical specifications

VT416 / DC current monitor
DimensionsSize 102 × 52 x 26 mm
Weight160 g
InputsRJ-9 / 2EDGK-7.5
Operating temperatureMin. -10° C - Max.80° C
Operating humidityMin. 5% - Max. 95% (Non-Condensing)
Power input12V DC
Mounting

Desktop, Wall mount

Power Consumption100 mW
ComponentsManufactured in EU.
Max. distance m50 m
Special FeaturesIsolation - 2,5 kV, Measured range ±8 A, Accuracy - 1%, Output 0-5 V.
HS Code9030 33 100

...