Function and purpose

Switchable contact. Can be used together with equipment, for example for switching ON/OFF air conditioners. Can control manage 5A power for magnetic locks, bolt locks, solenoid electromagnets, siren, light source, heater and etc.

Can be connected to units that have 12V outputs.

Website link: VT11 / Dry Contact OutRelay output

Package includes

Package content can be found at : VT11 package content

LED indication

The senor has red LED indicator which sticks from the top cover


NormalReverse
contact is closedRed-
contact is open-Red

Connecting switchable contact

Switchable contact can only be connected to 12V 0.25A outputs of Vutlan monitoring system.The diagram below explains how to connect two VT11 switchable contacts to the monitoring system.

Usage examples with installation diagram

Example 1. Using "VT11 / dry contact output" to control a device with dry contact input.

...

Example 3. Control magnetic lock, electric motor, solenoid electromagnet

 

Cable pinouts

Switchable contact uses standard two wire cable for connecting to the monitoring unit.

Technical specifications

VT590
Dimensions60×18×18 mm
Weight60 g
Input

wire terminal 3.81mm 2P

Outputswire terminal 5.0mm 2P
Operating temperatureTemperature : Min. -50 °C - Max.105 °C
Operating humidityHumidity : Min. 5% - Max. 95% (Non-Condensing)
MountingMounting bracket,sticker and screws are included.
Power consumption12 mW
Max. distance m200 m
HS Code9025 11 800
ComponentsManufactured in E.U.
Special featuresCan be connected to any monitoring system or device with 12V outputs.
Max. switching voltage250VAC / 30VDC
Max switching current5A
Max. switching power1250VA / 150W
Min. contact loadNo gold plated: 5VDC 10mA

...