Function and purpose
Unique long-term stability
Advanced particle size binning
Superior precision in mass concentration and number concentration sensing
...
The maximum amount of VT580 sensors connected to the Vutlan monitoring unit and maximum length can be extended using the "VT408 / Sensor extension unit" or “VT408DIN / Extension unit”.
Connecting the sensor
The sensor can be connected to the system's available analog ports. See the picture below.
...
The sensor can also be connected to the “VT408DIN / Extension unit”.
Technical specifications
General parameters | Description |
Type: | Analog sensor |
Usage: | For Air quality and pollution monitoring. |
Technology: | Laser scattering based on contamination-resistance technology with optical particle counters (OPCs) |
Daisy chain connection: | Not possible |
Sensor parameters | |
Mass concentration precision | ±10 % |
Mass concentration range | 0 - 1000 μg/m³ |
Lifetime | more than 10 years |
Particle size range | 0.3 to 10.5 μm |
Hardware parameters | Description/value |
Best used in temperatures | from +10° С to +40°C |
Best used in humidity | from 20% RH to 80% RH |
Operating Temperature: | -10 to +60°C |
Storage temperature: | -40 to +70°C |
Operating humidity: | 0 to 95% RH |
Power Consumption: | Max. 400 mW in operation mode, |
Installation | |
Cable length: | 2 m |
Mounting possibilities: | Wall or ceiling mount |
Output terminal: | RJ-11 / 6P4C |
Max. distance from the unit: | 100 meters from Vutlan controller or from “VT408 / extension unit” or from “VT408DIN / DIN extension unit” |
Other | |
Manufactured in (country): | Manufactured in Slovak Republic, E.U. |
Certification standards: | MCERTS-certified |
HS Code: | 9027102000 |
Drawings
VT580 dimensions:
...
Installation
1. Press the sensor (without the top cover) against the wall or ceiling. Draw two dots using a pencil where the holes will be drilled.
...
2. Drill two holes in the wall. Insert plastic dowels. Use two screws to screw the sensor to the wall or ceiling. Close the Top cover.
...
Package includes
Include Page | ||||
---|---|---|---|---|
|
Analog sensor connection
Linked page Analog sensors connection
Sensor configuration
Linked page Sensor configuration
Technology
'VT580 Dust Particle sensor' sensors are optical particle counters (OPCs) based on laser scattering. All OPCs guide ambient, suspended particles to a measurement cell inside the device. The measurement cell consists of a light source (e.g., a laser) and a photodetector. Due to the interaction of particles and light, part of the incoming light is scattered towards the nearby photodetector. The collected signal is converted into real-time particle count and mass concentration values, respectively given in #/cm3 and in μg/m3.
...