Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Table of Contents
stylenone

Documentation page: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/3315859457/VT580+Dust+particles+sensor

Product page:

VT580 dust particle sensor air pollution quality particulate matter detector probe monitoring and control by Vutlan-09.jpgVT580 dust particle sensor air pollution quality particulate matter detector probe monitoring and control by Vutlan-10.jpg
VT580 dust particle sensor air pollution quality particulate matter detector probe monitoring and control by Vutlan-13.jpgVT580 dust particle sensor air pollution quality particulate matter detector probe monitoring and control by Vutlan-08.jpg

Function and purpose

  • Unique long-term stability

  • Advanced particle size binning

  • Superior precision in mass concentration and number concentration sensing

...

The maximum amount of VT580 sensors connected to the Vutlan monitoring unit and maximum length can be extended using the "VT408 / Sensor extension unit" or “VT408DIN / Extension unit”.

Connecting the sensor

  1. The sensor can be connected to the system's available analog ports. See the picture below.

...

  1. The sensor can also be connected to the “VT408DIN / Extension unit”.

Technical specifications

General parameters

Description

Type:

Analog sensor

Usage:

For Air quality and pollution monitoring.

Technology:

Laser scattering based on contamination-resistance technology with optical particle counters (OPCs)

Daisy chain connection:

Not possible

Sensor parameters

Mass concentration precision

±10 %

Mass concentration range

0 - 1000 μg/m³

Lifetime

more than 10 years

Particle size range

0.3 to 10.5 μm

Hardware parameters

Description/value

Best used in temperatures

from +10° С to +40°C

Best used in humidity

from 20% RH to 80% RH

Operating Temperature:

-10 to +60°C

Storage temperature:

-40 to +70°C

Operating humidity:

0 to 95% RH

Power Consumption:

Max. 400 mW in operation mode,

Installation

Cable length:

2 m

Mounting possibilities:

Wall or ceiling mount

Output terminal:

RJ-11 / 6P4C

Max. distance from the unit:

100 meters from Vutlan controller or from “VT408 / extension unit” or from “VT408DIN / DIN extension unit

Other

Manufactured in (country):

Manufactured in Slovak Republic, E.U.

Certification standards:

MCERTS-certified

HS Code:

9027102000

Drawings

VT580 dimensions:

...

Installation

1. Press the sensor (without the top cover) against the wall or ceiling. Draw two dots using a pencil where the holes will be drilled.

...

2. Drill two holes in the wall. Insert plastic dowels. Use two screws to screw the sensor to the wall or ceiling. Close the Top cover.

...

Package includes

Include Page
VT580 package content
VT580 package content

Analog sensor connection

Linked page Analog sensors connection

Sensor configuration

Linked page Sensor configuration

Technology

'VT580 Dust Particle sensor' sensors are optical particle counters (OPCs) based on laser scattering. All OPCs guide ambient, suspended particles to a measurement cell inside the device. The measurement cell consists of a light source (e.g., a laser) and a photodetector. Due to the interaction of particles and light, part of the incoming light is scattered towards the nearby photodetector. The collected signal is converted into real-time particle count and mass concentration values, respectively given in #/cm3 and in μg/m3.

...