The sensor detects water by increasing capacitance on two metal poles. The detector is encapsulated in plastic housing. Due to the low applied voltages and the applied leakage detection principle, it does not rust over time.

Product page: https://vutlan.com/analog-sensors/169-vt593-spot-leak-sensor.html

...

Other installation examples of similiar similar sensors for leak detection can be found in our articles "Water leakage detection using cable sensor and spot sensor" and "Leak detection under raised floors in data centers".

...

VT593 / Spot leak sensor specifications

Description

The sensor has two RJ connectors. RJ 6P4C connects to the analog port of Vutlan monitoring system. RJ 4P2C connects the leak detector with two poles.

Dimensions

60×18×18 mm

Weight

60 g

Input

2 wire (WDC cable)

Detection

Capacitive

Output

RJ11 / RJ12 (6p4c)

Operating temperature

-10 °C to +80 °C

Operating humidity

5% to 95% (Non-Condensing)

Mounting

Mounting bracket included.

Power consumption

60mW

Max. distance m

100 m

HS Code

9025 80 400

Components

Manufactured in E.U.

Special features

Response time: 15 sec., Recovery time: Depends on how fast the sensor dries out

...