VT335t, VT336t, VT825t, VT825tt, VT855t, VT855tt, VT960t and VT960tt are the monitoring units and can not connect to each other. For scalability please use extension units and embedded boards.
...
● Built-in □ None ♦ Extension possible ◊ Not extendable
Versions |
---|
Device Management: Web, SNMP | Yes | Yes | Yes | Yes | Yes |
Yes
Sensor access: Three-level by login |
Yes | Yes | Yes | Yes | Yes | |
Interface |
LAN: Ethernet 10/100 Mbit | Yes | Yes | Yes | Yes | Yes |
Yes
OS: Linux |
v.6.2 | v.6.2 | v.6.2 | v.6.2 | v.6.2 | |
Interface: Any browser |
Yes | Yes | Yes | Yes | Yes | |
Memory RAM: |
1 Gb
128 Mb | 128 Mb | 128 Mb | 128 Mb | 128 Mb |
CPU speed: |
720 MHz
1 GHz | 720 MHz | 720 MHz | 720 MHz | 600 MHz |
Total CPU cores: |
2 | 2 | 2 | 2 | 2 | |
Clock: Built-in clock |
Yes | Yes | Yes | Yes | Yes | |
Timer: Built-in watchdog |
Yes | Yes | Yes | Yes | Yes | |
The maximum amount of sensors: physical sensors, dry contacts, relays |
400
150 | 130 | 100 | 100 | 100 |
The maximum amount of elements: notifications, triggers, timers, logic, sensors, dry contacts, SNMP Get, SNMP Trap, Dial task, and other elements |
2000
1000 | 1000 | 700 | 700 | 700 | |
Networking / Protocol support |
LTE Gateway mode: Internet access (routing for internal network) (modem ordered separately) |
Yes | Yes | Yes | Yes | No | |
LTE Access mode: Internet access over LTE (modem ordered separately) |
Yes | Yes | Yes | Yes | No | |
Network protocols: DHCP; HTTP; HTTPS; SNMP v1, v2c, v3; SMTP; FTP; Syslog; TLS; | Yes | Yes | Yes | Yes | Yes |
Yes
Modbus RTU |
Using extension VT485m | Using extension VT485m | Using extension VT485m | Using extension VT485m | No | |
RS485 / OSDPv2: reader access control |
Yes | Yes | Yes | Yes | No | |
Modbus TCP / IP |
Yes | Yes | Yes | Yes | Yes | |
Static routing | Yes | Yes | Yes | Yes |
Yes
Dynamic DynDNS | Yes | Yes | Yes | Yes | Yes |
Yes
Access via RADIUS server | Yes | Yes | Yes | Yes | Yes |
Yes
VPN: secure data communications; secure change of connection between LTE and LAN | Yes | Yes | Yes | Yes |
Yes
No |
SSL installation |
Yes | Yes | Yes | Yes | Yes | |
NTP server |
Yes | Yes | Yes | Yes | Yes | |
Alerts / Notifications |
Alert types: E-mail, FTP log, Syslog, SMTP, SNMP Traps, SMS (Modem is ordered separately), Web-to-SMS, | Yes | Yes | Yes | Yes | Yes |
Yes
A maximum number of "mail to" recipients in an E-mail notification: |
50
20 | 20 | 20 | 20 | 20 |
A maximum number of "SMS to" recipients in an SMS notification: also the maximum amount of phone numbers |
50
20 | 20 | 20 | 20 | ||
Virtual sensors |
Pings: Built-in function for server pinging. Test the reachability of a host in a network. |
Yes | Yes | Yes | Yes | Yes | |
IP cameras: Connect the IP MJPEG camera with a proxy via the master module. Only view, no record. |
4 | 4 | 4 | 4 | 4 | |
Get SNMP: Read data from external equipment via SNMP PDU GET (v1/2c) |
Yes | Yes | Yes | Yes | Yes | |
User keys: Add users who have access using an RFID reader. | Yes | Yes | Yes | Yes |
Yes
No | |||||
Logic schemes: Used to specify automatic actions to events that occur in the system. | Yes | Yes | Yes | Yes | Yes |
Yes
Timers: Allows you to plan the events in the system. | Yes | Yes | Yes | Yes | Yes |
Yes
Triggers: Generate events in the system if logic is triggered. |
Yes | Yes | Yes | Yes | Yes | |
SNMP traps |
Yes | Yes | Yes | Yes | Yes | |
Virtual Math element (combine several sensor data and calculate new data) |
Yes | Yes | Yes | Yes | Yes | |
Logic schemes | Yes | Yes | Yes | Yes | Yes |
Yes
Modbus TCP/IP: read/write | Yes | Yes | Yes | Yes | Yes |
Yes
Power |
Power input (230V AC): |
x2 inputs option | x2 inputs option | No | No | No | |
Power input (24 ÷ 48V DC): | x2 inputs |
option | x2 inputs option | No | No | No |
Power input (12V DC): |
x1 input option | x1 input option | x2 inputs | x2 inputs | Input | |
Fuse: Fuse at the inlet |
1 A | 1 A | PTC | PTC | PTC | |
Min. power consumption: |
6W
1 W | 1 W | 1 W | 1 W | 1 W |
Max. power consumption: |
30 W
10 W | 10 W | 10 W | 10 W | 6 W |
The maximum current load on the relay: | 10А | 10А |
10А
250mА | 250mА | 250mА | |
Redundant power supply: built-in voltage monitor, voltage range 9-12.6V. | Yes AC/DC DC/DC | Yes AC/DC DC/DC | Yes |
AC/DC
DC/DC | Yes DC |
Yes
DC12V | - | ||||
Outputs |
Relay outputs: latching relays 240V*10A |
2 | 2 | - | - | - | |
Relays outputs: 12V 0.25A | 2 | 2 | 2 | 2 | 2 |
2
Max. dry contact outputs (contact closures/digital outputs) | 8 |
8
- | 5 | - | - | ||
Inputs |
Analog port: 6P6C for connection of an analog sensor. (extendable using CAN bus) | 8 built-in ports, extended using extension unit | 8 built-in ports, extended using extension unit |
8 built-in ports,
extended using extension unit
4 built-in ports, | 4 built-in ports, extended using extension unit | 4 built-in ports, extended using extension unit |
CAN port: Max number of sensors Use CAN-12V-1A for connecting more than 12 devices. |
x1 port, max. 32 devices
x2 port, max. 362 devices | x1 port, max. 32 devices | x1 port, max. 32 devices | x1 port, max. 32 devices | x1 port, max. 10 devices |
Dry contact inputs: (contact closures/digital inputs) |
32 | 16 | 8 | 4 | 2 | |
Modbus RTU (RS-485): Max. line length 1000m | Using extension VT485m | Using extension VT485m | Using extension VT485m | Using extension VT485m |
Using extension VT485m
- |
OSDP v2 reader extension: |
Using extension VT485R | Using extension VT485R | Using extension VT485R | Using extension VT485R | - | |
Video |
USB cameras |
x2
x1 | x1 | x1 | x1 | x1 | |
IP cameras | x4 | x4 | x4 | x4 | x4 |
x4
RTSP IP camera |
- | - | - | - | - | |
Other connectors |
Ethernet port: 10/100Mbit | x1 | x1 | x1 | x1 | x1 |
x1
Ethernet port: 10/100/1000Mit |
x1
- | - | - | - | - |
USB 2.0 Type A |
- | - | - | - | - | |
USB 2.0 micro |
x1 | x1 | x1 | x1 | x1 | |
Switch Normal / Recovery: returns the device to factory settings |
Yes | Yes | Yes | Yes | Yes | |
External Memory / Logs |
Micro SD memory card slot (SDXC up to 512 Gb) | Yes | Yes | Yes | Yes | Yes |
Yes
SD card formatting function (FAT32) | Yes | Yes | Yes | Yes | Yes |
Yes
USB flash drive: logs, sensor readings, item settings, etc. |
Yes | Yes | Yes | Yes | Yes | |
Send system log to e-mail: Logs, sensor data, elements settings, etc. |
Yes | Yes | Yes | Yes | Yes | |
Sensor dump files: save the per-second samples of analog and discrete sensors | Yes | Yes | Yes | Yes | Yes |
Yes
Yes | Yes | Yes | Yes | Yes |
Yes
Send to FTP server: Logs, sensor data, elements settings, etc. |
Yes | Yes | Yes | Yes | Yes | |
Maximum amount of log files: 10,000 logs/days = 27 years |
Yes | Yes | Yes | Yes | Yes | |
Sample rate/period (logs, graphs) |
1 s | 1 s | 1 s | 1 s | 1 s | |
Modem (extension ordered separately) |
4G LTE modem: ordered separately. |
- | ||||
Modem modes:
| Gateway / Access / SMS | Gateway / Access / SMS | Gateway / Access / SMS | Gateway / Access / SMS |
Gateway / Access / SMS
- | ||||
Modem LED: STATUS | Yes | Yes | Yes | Yes |
Yes
- | |||||
Embedded onboard sensors |
Temperature sensor: +/- 1 °C PCB temperature. | Yes | Yes | Yes | Yes | Yes |
Yes
Power supply voltage sensor: Accuracy (1%) |
Main & Reserve | Main & Reserve | Main & Reserve | Main & Reserve | Yes | |
LED indication |
Ethernet LAN: LINK | Yes | Yes | Yes | Yes | Yes |
Yes
Ethernet LAN: ACT |
Yes | Yes | Yes | Yes | Yes | |
CAN bus: STATUS |
Yes | Yes | Yes | Yes | Yes | |
System: STATUS (ACT) | Yes | Yes | Yes | Yes | Yes |
Yes
System: ERROR (ERR) | Yes | Yes | Yes | Yes | Yes |
Yes
System: ALARM |
Yes | Yes | Yes | Yes | Yes | |
12V 0.25A outputs: STATUS (e.g. E1, E2) |
x2 | x2 | x2 | x2 | x2 | |
MODBUS RTU: STATUS |
VT485M | VT485M | VT485M | VT485M | - | |
ODSP Reader. | VT485R | VT485R | VT485R | VT485R |
VT485R
- | ||
NC/NO/COM Relay (e.g. R1, R2) | x2 | x2 |
x2
- | - | - | |||
Environmental characteristics |
Operating temperature: -10 to 80 °C |
Yes | Yes | Yes | Yes | Yes | |
Storage temperature: –25 to 85 °C |
Yes | Yes | Yes | Yes | Yes | |
Operating humidity: 0 to 90 %, non-condensing | Yes | Yes | Yes | Yes | Yes |
Yes
Storage humidity: 0 to 95 %, non-condensing | Yes | Yes | Yes | Yes | Yes |
Yes
Other Features |
Installation: |
19” 1U | 19” 1U | DIN rail, Wall | Desktop | Desktop | |
Casing: | Sheet metal | Sheet metal |
Sheet metal
Plastic | Sheet metal | Plastic |
Dimensions (L x W x H) in mm: |
440x44x90 | 440x44x90 | L_212.5 H_90.1 D_32.20 | 180x35x80 | 150x29x100 | |
Weight: |
1,6 kg | 1,5 kg | 0,7 kg | 0,5 kg | ||
External chassis grounding: M4 thread |
Yes | Yes | Yes | Yes | Yes | |
Web interface (panels) |
Dashboard panel: |
Yes | Yes | Yes | Yes | Yes | |
Overall statistics panel: |
Yes | Yes | Yes | Yes | Yes | |
System tree panel: sensors and devices displayed in a hierarchy |
Yes | Yes | Yes | Yes | Yes | |
Dry outputs panel: | Yes | Yes | Yes |
Yes
No | Yes | ||||
Dry inputs panel: | Yes | Yes | Yes | Yes | Yes |
Yes
Event log panel: amount of logs |
500
300 | 300 | Yes | 300 | 200 | |
Logic schemes panel: | Yes | Yes | Yes | Yes | Yes |
Yes
Cameras panel: |
Yes | Yes | Yes | Yes | Yes | |
Map panel: 5 layers |
Yes | Yes | Yes | Yes | Yes | |
Users panel: | Yes | Yes | Yes | Yes | Yes |
Yes
CAN configuration panel: | Yes | Yes | Yes | Yes | Yes |
Yes
Graphs panel: | Yes | Yes | Yes | Yes | Yes |
Yes
Reset smoke detectors panel: | Yes | Yes | Yes | Yes | Yes |
Yes
Preferences panel: Web GUI, Network, Time, Logging, DynDNS, SNMP, RADIUS, FTP backup, VPN Clent, Modbus RTU, GPS, SMTP, Routing | Yes | Yes | Yes | Yes | Yes |
Yes
System menu panel: About, Firmware, Export, Support |
Yes | Yes | Yes | Yes | Yes | |
List of latest sent SMS messages: |
500
200 | 200 | Yes | 150 | 200 |
Analog sensor power reset: resets smoke sensors |
Yes | Yes | Yes | Yes | Yes |
● Built-in □ None ♦ Extension possible ◊ Not extendable