By default, the terminator on the board of VT336 and VT336PoE is always ON. The cap is inserted between the two contacts providing 120R resistance. The terminator is a J16 connector on the board.

...

  • Sensors are connected in a daisy chain connection.

  • 120Ω resistor is used at the end of the chain which is equal to the resistance of the cable.

  • A twisted pair cable is used for A(+) and B(-).

  • "VT336 and VT336PoE / DIN monitoring units" have an internal termination and by default, it is switched to ON position. (If required possible to switch OFF)

  • Up to 32 devices can be used.

  • Overall cable length is no more than 1000 meters.

...

  • Switch off the Vutlan monitoring unit.

  • Open the enclosure’s bottom and pull the mainboard from the enclosure.

  • Find a Modbus jumper and take the cap off.

  • Put everything back together.

...