VT335i, VT336, VT825i, VT825ii, VT855i, VT855ii, VT960i, and VT960ii are the monitoring units and can not connect to each other. For scalability please use extension units and embedded boards.
...
● Built-in □ None ♦ Extension possible ◊ Not extendable
Versions | |||||||||
---|---|---|---|---|---|---|---|---|---|
Device Management: Web, SNMP, manually via SMS | Yes | Yes | Yes | Yes | Yes | Yes | |||
Sensor access: Three-level by login | Yes | Yes | Yes | Yes | Yes | Yes | |||
Interface | |||||||||
LAN: Ethernet 10/100 Mbit | Yes | Yes | Yes | Yes | Yes | Yes | |||
OS: Linux | v.5.10 | v.6.2 | v.6.2 | v.6.2 | v.6.2 | v.6.2 | |||
Interface: Any browser | Yes | Yes | Yes | Yes | Yes | Yes | |||
Memory RAM: | 1 Gb | 128 Mb | 128 Mb | 128 Mb | 128 Mb | 128 Mb | |||
CPU speed: | 720 MHz | 1 GHz | 720 MHz | 720 MHz | 720 MHz | 600 MHz | |||
Total CPU cores: | 4 | 2 | 2 | 2 | 2 | 2 | |||
Clock: Built-in clock | Yes | Yes | Yes | Yes | Yes | Yes | |||
Timer: Built-in watchdog | Yes | Yes | Yes | Yes | Yes | Yes | |||
The maximum amount of sensors: physical sensors, dry contacts, relays | 400 | 150 | 130 | 100 | 100 | 70100 | |||
The maximum amount of elements: notifications, triggers, timers, logic, sensors, dry contacts, SNMP Get, SNMP Trap, Dial task, and other elements | 2000 | 1000 | 1000 | 700 | 700 | 700 | |||
Networking / Protocol support | |||||||||
LTE Gateway mode: Internet access (routing for internal network) (modem ordered separately) | Yes | Yes | Yes | Yes | YesYes | No | |||
LTE Access mode: Internet access over LTE (modem ordered separately) | Yes | Yes | Yes | Yes | YesYes | No | |||
Network protocols: DHCP; HTTP; HTTPS; SNMP v1, v2c, v3; SMTP; FTP; Syslog; TLS; | Yes | Yes | Yes | Yes | Yes | Yes | |||
Modbus RTU | Yes | Yes | NoYes | Yes | NoYes | No | |||
RS485 / OSDPv2: reader access control | NoYesNo | Yes | NoYes | Yes | NoYes | No | |||
Modbus TCP / IP | Yes | Yes | Yes | Yes | Yes | NoYes | |||
Static routing | Yes | Yes | Yes | Yes | Yes | ||||
Dynamic DynDNS | Yes | Yes | Yes | Yes | Yes | Yes | |||
Access via RADIUS server | Yes | Yes | Yes | Yes | Yes | Yes | |||
VPN: secure data communications; secure change of connection between LTE and LAN | Yes | Yes | Yes | Yes | Yes | No | |||
SSL installation | Yes | Yes | Yes | Yes | Yes | Yes | |||
NTP server | Yes | Yes | Yes | Yes | Yes | Yes | |||
Alerts / Notifications | |||||||||
Alert types: E-mail, FTP log, Syslog, SMTP, SNMP Traps, SMS (Modem is ordered separately), Web-to-SMS, | Yes | Yes | Yes | Yes | Yes | Yes | |||
A maximum number of "mail to" recipients in an E-mail notification: | 50 | 20 | 20 | 20 | 20 | 20 | |||
A maximum number of "SMS to" recipients in an SMS notification: also the maximum amount of phone numbers | 50 | 20 | 20 | 20 | 20 | 20 | |||
Virtual sensors | |||||||||
Pings: Built-in function for server pinging. Test the reachability of a host in a network. | Yes | Yes | Yes | Yes | Yes | Yes | |||
IP cameras: Connect the IP MJPEG camera with a proxy via the master module. Only view, no record. | 4 | 4 | 4 | 4 | 4 | 4 | |||
Get SNMP: Read data from external equipment via SNMP PDU GET (v1/2c) | Yes | Yes | Yes | Yes | Yes | Yes | |||
User keys: Add users who have access using an RFID reader. | Yes | Yes | Yes | Yes | NoYes | No | |||
Logic schemes: Used to specify automatic actions to events that occur in the system. | Yes | Yes | Yes | Yes | Yes | Yes | |||
Timers: Allows you to plan the events in the system. | Yes | Yes | Yes | Yes | Yes | Yes | |||
Triggers: Generate events in the system if logic is triggered. | Yes | Yes | Yes | Yes | Yes | Yes | |||
SNMP traps | Yes | Yes | Yes | Yes | Yes | Yes | |||
Virtual Math element (combine several sensor data and calculate new data) | Yes | Yes | Yes | Yes | Yes | Yes | |||
Logic schemes | Yes | Yes | Yes | Yes | Yes | Yes | |||
Modbus TCP/IP: read/write | Yes | Yes | Yes | Yes | Yes | NoYes | |||
Power | |||||||||
Power input (230V AC): | x2 inputs option | x2 inputs option | x2 inputs option | No | No | No | |||
Power input (24 ÷ 48V DC): | x2 inputs option | x2 inputs option | x2 inputs option | No | No | No | |||
Power input (12V DC): | No | x1 input option | x1 input option | x2 inputs | x2 inputs | Input | |||
Fuse: Fuse at the inlet | 1 A | 1 A | 1 A | 1 A | 1 A | No | |||
Min. power consumption: | 1 W | 1 W | |||||||
Max. power consumption: | 30 W | 10 W | 10 W | 10 W | 10 W | 6 W | |||
The maximum current load on the relay: | 10А | 10А | 10А | 250mА | 250mА | 250mА | |||
Redundant power supply: built-in voltage monitor, voltage range 9-12.6V. | Yes AC/DC DC/DC | Yes AC/DC DC/DC | Yes AC/DC DC/DC | Yes DC/DC | Yes DC 12V | - | |||
Outputs | |||||||||
Relay outputs: latching relays 240V*10A | 2 | 2 | 2 | - | - | - | |||
Relays outputs: 12V 0.25A | 2 | 2 | 2 | 2 | 2 | 2 | |||
Max. dry contact outputs (contact closures/digital outputs) | 8 | 8 | - | 5 | - | - | |||
Inputs | |||||||||
Analog port: 6P6C for connection of an analog sensor. (extendable using CAN bus) | 8 built-in ports, extended using extension unit | 8 built-in ports, extended using extension unit | 8 built-in ports, extended using extension unit | 4 built-in ports, | 4 built-in ports, extended using extension unit | 4 built-in ports, extended using extension unit | |||
CAN port: Max number of sensors Use CAN-12V-1A for connecting more than 12 devices. | x1 port, max. 32 devices | x1 port, max. 32 devices | x1 port, max. 32 devices | x1 port, max. 32 devices | x1 port, max. 32 devices | x1 port, max. 10 devices | |||
Dry contact inputs: (contact closures/digital inputs) Extadable using CAN bus and Dry contacts unit | 32 | 32 | 16 | 8 | 4 | 2 | |||
Modbus RTU (RS-485): Max. line length 1000m | 1 built-in port, up to 50 sensors | 1 built-in port, up to 50 sensors | - | Using extension VT485m | - | - | |||
OSDP v2 reader extension: | - | - | - | - | - | - | |||
Video | |||||||||
AV camera | x1 | - | - | - | - | - | |||
USB cameras | x2 | x1 | x1 | x1 | x1 | x1 | |||
IP cameras | x4 | x4 | x4 | x4 | x4 | x4 | |||
RTSP IP camera | x1 | - | - | - | - | - | |||
Other connectors | |||||||||
Ethernet port: 10/100Mbit | x1 | x1 | x1 | x1 | x1 | x1 | |||
USB 2.0 Type A | x1 | x1 | x1 | - | - | - | |||
USB 2.0 micro | x1 | x1 | x1 | x1 | x1 | x1 | |||
Switch Normal / Recovery: returns the device to factory settings | □ | Yes | Yes | Yes | Yes | Yes | |||
External Memory / Logs | |||||||||
Micro SD card slot (SDXC up to 512 Gb) | Yes | Yes | Yes | Yes | Yes | 64Gb | |||
SD card formatting function (FAT32) | Yes | Yes | Yes | Yes | Yes | Yes | |||
USB flash drive: logs, sensor readings, item settings, etc. | Yes | Yes | Yes | Yes | Yes | Yes | |||
Send system log to e-mail: Logs, sensor data, elements settings, etc. | Yes | Yes | Yes | Yes | Yes | Yes | |||
Sensor dump files: save the per-second samples of analog and discrete sensors | Yes | Yes | Yes | Yes | Yes | Yes | |||
Yes | Yes | Yes | Yes | Yes | Yes | ||||
Send to FTP server: Logs, sensor data, elements settings, etc. | Yes | Yes | Yes | Yes | Yes | Yes | |||
Maximum amount of log files: 10,000 logs/days = 27 years | Yes | Yes | Yes | Yes | Yes | Yes | |||
Sample rate/period (logs, graphs) | 1 s | 1 s | 1 s | 1 s | 1 s | 1 s | |||
Modem (extension ordered separately) | |||||||||
4G LTE modem: ordered separately. | - | ||||||||
Modem modes:
| Gateway / Access / SMS | Gateway / Access / SMS | Gateway / Access / SMS | Gateway / Access / SMS | Gateway / Access / SMS | - | |||
Modem LED: STATUS | Yes | Yes | Yes | Yes | Yes | - | |||
Embedded onboard sensors | VT325t | ||||||||
Temperature sensor: +/- 1 °C PCB temperature. | Yes | Yes | Yes | Yes | Yes | Yes | |||
Power supply voltage sensor: Accuracy (1%) | 1 | Main & Reserve | Main & Reserve | Main & Reserve | Main & Reserve | Yes | |||
LED indication | |||||||||
Ethernet LAN: LINK | Yes | Yes | Yes | Yes | Yes | Yes | |||
Ethernet LAN: ACT | Yes | Yes | Yes | Yes | Yes | Yes | |||
CAN bus: STATUS | Yes | Yes | Yes | Yes | Yes | Yes | |||
System: STATUS (ACT) | Yes | Yes | Yes | Yes | Yes | Yes | |||
System: ERROR (ERR) | Yes | Yes | Yes | Yes | Yes | Yes | |||
System: ALARM | - | Yes | Yes | Yes | - | Yes | |||
12V 0.25A outputs: STATUS (e.g. E1, E2) | x2 | x2 | x2 | Yes | x2 | x2 | |||
MODBUS RTU: STATUS | VT485M | VT485M | VT485M | - | VT485M | - | |||
ODSP Reader. | VT485R | VT485R | VT485R | - | VT485R | - | |||
NC/NO/COM Relay (e.g. R1, R2) | x2 | x2 | x2 | - | - | - | |||
HDD: Hard drive STATUS | Yes | - | - | - | - | - | |||
Environmental characteristics | |||||||||
Operating temperature: -10 to 80 °C | Yes | Yes | Yes | Yes | Yes | Yes | |||
Storage temperature: –25 to 85 °C | Yes | Yes | Yes | Yes | Yes | Yes | |||
Operating humidity: 0 to 90 %, non-condensing | Yes | Yes | Yes | Yes | Yes | Yes | |||
Storage humidity: 0 to 95 %, non-condensing | Yes | Yes | Yes | Yes | Yes | Yes | |||
Other Features | |||||||||
Installation: | 19” 1U | 19” 1U | 19” 1U | DIN rail, Wall | Desktop | Desktop | |||
Casing: | Sheet metal | Sheet metal | Sheet metal | Plastic | Sheet metal | Plastic | |||
Dimensions (L x W x H) in mm: | 440x44x120 | 440x44x90 | 440x44x90 | L_212.5 H_90.1 D_32.20 | 180x35x80 | 150x29x100 | |||
Weight: | 2 kg | 1,6 kg | 1,5 kg | 0,7 kg | 0,5 kg | ||||
External chassis grounding: M4 thread | Yes | Yes | Yes | Yes | Yes | Yes | |||
Web interface (panels) | |||||||||
Dashboard panel: | Yes | Yes | Yes | Yes | Yes | Yes | |||
Overall statistics panel: | Yes | Yes | Yes | Yes | Yes | Yes | |||
System tree panel: sensors and devices displayed in a hierarchy | Yes | Yes | Yes | Yes | Yes | Yes | |||
Dry outputs panel: | Yes | Yes | Yes | Yes | No | Yes | |||
Dry inputs panel: | Yes | Yes | Yes | Yes | Yes | Yes | |||
Event log panel: amount of logs | 500 | 300 | 300 | Yes | 300 | 200 | |||
Logic schemes panel: | Yes | Yes | Yes | Yes | Yes | Yes | |||
Cameras panel: | Yes | Yes | Yes | Yes | Yes | Yes | |||
Map panel: 5 layers | Yes | Yes | Yes | Yes | Yes | Yes | |||
Users panel: | Yes | Yes | Yes | Yes | Yes | Yes | |||
CAN configuration panel: | Yes | Yes | Yes | Yes | Yes | Yes | |||
Graphs panel: | Yes | Yes | Yes | Yes | Yes | Yes | |||
Reset smoke detectors panel: | Yes | Yes | Yes | Yes | Yes | Yes | |||
Preferences panel: Web GUI, Network, Time, Logging, DynDNS, SNMP, RADIUS, FTP backup, VPN Clent, Modbus RTU, GPS, SMTP, Routing | Yes | Yes | Yes | Yes | Yes | Yes | |||
System menu panel: About, Firmware, Export, Support | Yes | Yes | Yes | Yes | Yes | Yes | |||
List of latest sent SMS messages: | 500 | 200 | 200 | Yes | 150 | 200 | |||
Analog sensor power reset: resets smoke sensors | Yes | Yes | Yes | Yes | Yes | Yes |
● Built-in □ None ♦ Extension possible ◊ Not extendable