Analog sensors connection
Analog sensors connection

How to test the sensor & sensor cable

  1. Connect the WLC cable to VT591. Connect VT591 to the analog port of the system. The sensor should appear in the Vutlan Web Interface >> “System tree” panel >> “System group” tab >> “Autodetect” sensors. Make sure that the WLC cable is straight or not contacting itself, or any conducting material. The sensor should appear in the system as “Normal” (if the behavior is set to “Normal”), which means that there’s no presence of liquid (the two yellow wires along the WLC cable are not cables shorted).

  2. Take a rag and wet it a little. Touch the rag to both yellow ires on the WLC cable. This should shorten the contact. The VT591 sensor should change the state to “Alarm”.

  3. Dry the cable carefully with a dry cloth.

Installation examples

Please find installation examples in our articles "Water leakage detection using cable sensor and spot sensor" and "Leak detection under raised floors in data centers".

...