VT335i, VT336, VT825i, VT825ii, VT855i, VT855ii, VT960i, and VT960ii are the monitoring units and can not connect to each other. For scalability please use extension units and embedded boards.
...
● Built-in □ None ♦ Extension possible ◊ Not extendable
Versions | VT325tVT335t | VT825t | VT855t | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Device Management: Web, SNMP, manually via SMS Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Sensor access: Three-level by login Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Interface | VT336t | VT335t | VT825t | VT855t | ||||||||
LAN: Ethernet 10/100 Mbit Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
OS: Linux | v.5.10 | v.56.402 | v.56.402 | v.56.402 | v.3.10v.6.2 | v.6.2 | v.6.2 | v.6.2 | ||||
Interface: Any browser Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Memory RAM: | 1 Gb | 128 Mb | 128 Mb | 64 128 Mb | 64 Mb | 128 128 Mb | 128 Mb | 128 Mb | 128 Mb | |||
CPU speed: | 720 MHz600 MHz | 1 GHz | 600 720 MHz | 720 MHz | 300 720 MHz | 600 MHz720 MHz | 720 MHz | 1 GHz | ||||
Total CPU cores: | 4 | 121 | 2 | 1 | 12 | 2 | 2 | 2 | 2 | |||
Clock: Built-in clock Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Timer: Built-in watchdog Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
The maximum amount of sensors: physical sensors, dry contacts, relays | 400 | 150150 | 130 | 100 | 30 | 100 | 15070 | 150 | 150 | |||
The maximum amount of elements: notifications, triggers, timers, logic, sensors, dry contacts, SNMP Get, SNMP Trap, Dial task, and other elements | 2000 | 1000 | 1000 | 700 | 500700 | 7001000 | 1000 | 1000 | ||||
Networking / Protocol support | VT325tVT335t | VT825t | VT855t | |||||||||
LTE Gateway mode: Internet access (routing for internal network) (modem ordered separately) | Yes | Yes | Yes | Yes | NoYes | Yes | Yes | Yes | ||||
LTE Access mode: Internet access over LTE (modem ordered separately) Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Network protocols: DHCP; HTTP; HTTPS; SNMP v1, v2c, v3; SMTP; FTP; Syslog; TLS; | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||
Modbus RTU | Yes | Yes | No | No | Yes | No | VT485m extension (Modbus or Reader) | VT485m extension (Modbus or Reader) | VT485m extension (Modbus or Reader) | |||
RS485 / OSDPv2: reader access control | No | No | No | No | No | No | VT485r extension (Modbus or Reader) | VT485r extension (Modbus or Reader) | VT485r extension (Modbus or Reader) | |||
Modbus TCP / Modbus TCP / IP | Yes | Yes | Yes | Yes | Yes | NoYes | Yes | Yes | ||||
Static routing Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||
Dynamic DynDNS Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Access via RADIUS server Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
VPN: secure data communications; secure change of connection between LTE and LAN | Yes | Yes | Yes | Yes | Yes | NoYes | Yes | Yes | ||||
SSL installation Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
NTP server Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Alerts / Notifications | VT325tVT335t | VT825t | VT855t | |||||||||
Alert types: E-mail, FTP log, Syslog, SMTP, SNMP Traps, SMS (Modem is ordered separately), Web-to-SMS, Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
A maximum number of "mail to" recipients in an E-mail notification: | 50 | 20 | 20 | 20 | 1020 | 20 | 20 | 20 | ||||
A maximum number of "SMS to" recipients in an SMS notification: also the maximum amount of phone numbers | 50 | 20 | 20 | 20 | 1020 | 20 | 20 | 20 | ||||
Virtual sensors | VT335t | VT825t | VT855t | |||||||||
Pings: Built-in function for server pinging. Test the reachability of a host in a network. Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
IP cameras: Connect the IP MJPEG camera with a proxy via the master module. Only view, no record. | 4 | 4 | 4 | 4 | 4 | 4 | 4 | 4 | ||||
Get SNMP: Read data from external equipment via SNMP PDU GET (v1/2c) Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
User keys: Add users who have access using an RFID reader. | Yes | Yes | Yes | No | Yes | NoYes | Yes | Yes | ||||
Logic schemes: Used to specify automatic actions to events that occur in the system. Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Timers: Allows you to plan the events in the system. Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Triggers: Generate events in the system if logic is triggered. Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
SNMP traps | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||
Virtual Math element (combine several sensor data and calculate new data) Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Logic schemes Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Modbus TCP/IP: read/write | Yes | Yes | Yes | Yes | Yes | NoYes | Yes | Yes | ||||
Power | VT325tVT335t | VT825t | VT855t | |||||||||
Power input (230V AC): | x2 inputs option | x2 inputs option | x2 inputs option | No | No | No | No | x2 inputs option | x2 inputs option | |||
Power input (24 ÷ 48V DC): | x2 inputs option | x2 inputs option | x2 inputs option | No | No | No | No | x2 x2 inputs option | x2 inputs option | |||
Power input (12V DC): | No | x1 input option | x1 input option | x2 inputs | x1 input | Inputx2 inputs | x1 input option | x1 input option | ||||
Fuse: Fuse at the inlet | 1 A | 1 A | 1 A | 1 A | -No | No | 1 A | 1 A | ||||
Min. power consumption: 1 W | 1 W | |||||||||||
Max. power consumption: | 30 W | 10 W | 10 W | 10 W | 12 W6 W | 6 W | 8 W | 10 W | ||||
The maximum current load on the relay: | 10А | 10А | 10А250mА | 250mА | 250mА | 250mА | 10А | 10А | ||||
Redundant power supply: built-in voltage monitor, voltage range 9-12.6V. | Yes AC/DC DC/DC | Yes AC/DC DC/DC | Yes AC/DC DC/DC | Yes DC 12V | - | -x2 12V DC | Yes AC/AC, AC/DC, DC/DC | Yes AC/AC, AC/DC, DC/DC | ||||
Outputs | VT325tVT335t | VT825t | VT855t | |||||||||
Relay outputs: latching relays 240V*10A | 2 | 2 | 2- | - | - | - | 2 | 2 | ||||
Relays outputs: 12V 0.25A 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | ||||
Max. dry contact outputs (contact closures/digital outputs) | 8 | 8- | - | - | - | - | - | 8 | ||||
Inputs | VT335t | VT825t | VT855t | |||||||||
Analog port: 6P6C for connection of an analog sensor. (extendable using CAN bus) | 8 built-in ports, | 8 built-in ports, | 8 built-in ports, | 4 built-in ports, | 6 built-in ports, | 4 built-in ports, | on the CAN bus extension unit8 built-in ports, | 8 built-in ports, | ||||
CAN port: Max number of sensors Use CAN-12V-1A for connecting more than 12 devices. | x1 port, max. 32 devices | x1 port, max. 32 devices | x1 port, max. 32 devices | x1 port, max. 32 devices | x1 port, max. 20 devices | x1 port, max. 10 devices | x1 port, max. 32 devices | x1 port, max. 32 devices | x2 ports, max. 32 devices | |||
Dry contact inputs: (contact closures/digital inputs) Extadable using CAN bus and Dry contacts unit | 32 | 32 | 16 | 4 | 4 | 2 | 4 | 16 | 32 | |||
Modbus RTU (RS-485): Max. line length 1000m | 1 built-in port, up to 50 sensors | 1 built-in port, up to 50 sensors | - | - | 1 built-in port, up to 50 sensors | - | Extension | -- | VT485m extension (Modbus or Reader), up to 50 sensors | |||
OSDP v2 reader extension: | - | - | - | - | - | -coming soon | coming soon | coming soon | ||||
Video | VT325tVT335t | VT825t | VT855t | |||||||||
AV camera | x1- | - | - | - | - | - | - | - | ||||
USB cameras | x2x1 | x1 | x1 | x1 | x1 | x1 | x1 | x1 | ||||
IP cameras x4 | x4 | x4 | x4 | x4 | x4 | x4 | x4 | x4 | ||||
RTSP IP camera | x1- | - | - | - | - | - | - | - | ||||
Other connectors | VT325tVT335t | VT825t | VT855t | |||||||||
Ethernet port: 10/100Mbit Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
USB 2.0 Type A | 1 | 1 | 1- | - | - | - | - | - | ||||
USB 2.0 micro 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | ||||
Switch Normal / Recovery: returns the device to factory settings | □Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
External Memory / Logs | VT335t | VT825t | VT855t | |||||||||
Micro SD card slot (SDXC up to 512 Gb) | Yes | Yes | Yes | Yes | No | 64GbYes | Yes | Yes | ||||
SD card formatting function (FAT32) | Yes | Yes | Yes | Yes | NoYes | Yes | Yes | Yes | ||||
USB flash drive: logs, sensor readings, item settings, etc. Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Send system log to e-mail: Logs, sensor data, elements settings, etc. Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Sensor dump files: save the per-second samples of analog and discrete sensors Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Send to FTP server: Logs, sensor data, elements settings, etc. Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Maximum amount of log files: 10,000 logs/days = 27 years | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||
Sample rate/period (logs, graphs) 1 s | 1 s | 1 s | 1 s | 1 s | 1 s | 1 s | 1 s | 1 s | ||||
Modem (extension ordered separately) | VT335t | VT825t | VT855t | |||||||||
4G LTE modem: ordered separately. | - | |||||||||||
Modem modes:
| Gateway / Access / SMS | Gateway / Access / SMS | Gateway / Access / SMS | Gateway / Access / SMS | Access / SMS | - | Gateway / Access / SMS | Gateway / Access / SMS | Gateway / Access / SMS | |||
Modem Modem LED: STATUS | Yes | Yes | Yes | Yes | Yes | -Yes | Yes | Yes | ||||
Embedded onboard sensors | VT325t | VT335t | VT825t | VT855t | ||||||||
Temperature sensor: +/- 1 °C PCB temperature. | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||
Power supply voltage sensor: Accuracy (1%) | 1 | Main & Reserve | Main & Reserve | Main & Reserve | 1 | Yes | Yes | Main & Reserve | Main & Reserve | |||
LED indication | VT335t | VT825t | VT855t | |||||||||
Ethernet LAN: LINK | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||
Ethernet LAN: ACT Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
CAN bus: STATUS Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
System: STATUS (ACT) Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
System: ERROR (ERR) Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
System: ALARM | - | Yes | Yes | - | Yes | Yes | Yes | Yes | Yes | |||
12V 0.25A outputs: STATUS (e.g. E1, E2) x2 | x2 | x2 | x2 | x2 | x2 | x2 | x2 | x2 | ||||
MODBUS RTU: STATUS | -VT485M- | VT485M | -VT485M- | VT485M | x1VT485M | - | - | - | - | |||
TX: Modbus data sent activity (Transmission)ODSP Reader. | YesVT485RYes | VT485R | -VT485R- | VT485R | -VT485R | - | - | - | Yes | |||
RX: Modbus data received activity (Receiving). | Yes | Yes | - | - | - | - | - | - | Yes | |||
NC/NO/COM Relay (e.g. R1, R2) | x2 | x2 | x2 | - | - | - | - | x2 | x2 | |||
HDD: Hard drive STATUS | Yes | - | - | - | - | - | - | - | - | |||
Environmental characteristics | VT325tVT335t | VT825t | VT855t | |||||||||
Operating temperature: -10 to 80 °C Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Storage temperature: –25 to 85 °C Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Operating humidity: 0 to 90 %, non-condensing Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Storage humidity: 0 to 95 %, non-condensing Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Other Features | VT325tVT335t | VT825t | VT855t | |||||||||
Installation: | 19” 1U | 19” 1U | 19” 1U | Desktop | DIN railDesktop | Desktop | 19” 1U | 19” 1U | ||||
Casing: | Sheet metal | Sheet metal | Sheet metal | Sheet metal | Plastic | PlasticSheet metal | Sheet metal | Sheet metal | ||||
Dimensions (L x W x H) in mm: | 440x44x120 | 440x44x90 | 440x44x90 | 180x35x80 | 160x90x58 | 150x29x100190x33x89 | 440x44x90 | 440x44x90 | ||||
Weight: | 2 kg | 1,6 kg | 1,5 kg | 0,7 kg | 0,4 kg | 0,5 kg0,7 kg | 1,5 kg | 1,6 kg | ||||
External chassis grounding: M4 thread | Yes | Yes | Yes | Yes | -Yes | Yes | Yes | Yes | ||||
Web interface (panels) | VT325tVT335t | VT825t | VT855t | |||||||||
Dashboard panel: Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Overall statistics panel: | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||
System tree panel: sensors and devices displayed in a hierarchy | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Dry outputs panel: | Yes | Yes | Yes | NoYes | Yes | Yes | Yes | Yes | ||||
Dry inputs panel: Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Event log panel: amount of logs | 500 | 300 | 300 | 300 | 200 | 200300 | 300 | 300 | ||||
Logic schemes panel: Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Cameras panel: Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Map panel: 5 layers Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Users panel: | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||
CAN configuration panel: Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Graphs panel: Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Reset smoke detectors panel: Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Preferences panel: Web GUI, Network, Time, Logging, DynDNS, SNMP, RADIUS, FTP backup, VPN Clent, Modbus RTU, GPS, SMTP, Routing | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||
System menu panel: About, Firmware, Export, Support Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
List of latest sent SMS messages: | 500 | 200 | 200 | 150 | 100 | 200 | 200 | 200 | 200 | |||
Analog sensor power reset: resets smoke sensors Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
● Built-in □ None ♦ Extension possible ◊ Not extendable