VT335i, VT336, VT825i, VT825ii, VT855i, VT855ii, VT960i, and VT960ii are the monitoring units and can not connect to each other. For scalability please use extension units and embedded boards.
...
Versions | VT825t | VT855t | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Device Management: Web, SNMP, manually via SMS | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Sensor access: Three-level by login | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Interface | VT336t | VT335t | VT825t | VT855t | |||||||||||
LAN: Ethernet 10/100 Mbit Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||||||
OS: Linux | v.5.10 | v.6.2 | v.6.2 | v.6.2 | v.6.2 | v.6.2 | v.6.2 | v.6.2 | |||||||
Interface: Any browser Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||||||
Memory RAM: | 1 Gb | 128 Mb | 128 Mb | 128 Mb | 128 Mb | 128 Mb | 128 Mb | 128 Mb | |||||||
CPU speed: | 720 MHz | 1 GHz | 720 MHz | 720 MHz | 720 MHz | 600 MHz720 MHz1 GHz | |||||||||
Total CPU cores: | 4 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | |||||||
Clock: Built-in clock | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Timer: Timer: Built-in watchdog Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||||||
The maximum amount of sensors: physical sensors, dry contacts, relays | 400 | 150 | 130 | 100 | 100 | 70150 | 150 | ||||||||
The maximum amount of elements: notifications, triggers, timers, logic, sensors, dry contacts, SNMP Get, SNMP Trap, Dial task, and other elements | 2000 | 1000 | 1000 | 700 | 700 | 700 | 1000 | 1000 | |||||||
Networking / Protocol support | VT825t | VT855t | |||||||||||||
LTE Gateway mode: Internet access (routing for internal network) (modem ordered separately) | Yes | Yes | Yes | Yes | NoYes | Yes | Yes | ||||||||
LTE Access mode: Internet access over LTE (modem ordered separately) Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||||||
Network protocols: DHCP; HTTP; HTTPS; SNMP v1, v2c, v3; SMTP; FTP; Syslog; TLS; | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Modbus RTU | Yes | Yes | No | No | Yes | No | VT485m extension (Modbus or Reader) | VT485m extension (Modbus or Reader) | |||||||
RS485 / OSDPv2: reader access control | No | No | No | No | No | No | VT485r extension (Modbus or Reader) | VT485r extension (Modbus or Reader) | |||||||
Modbus TCP / IP | Modbus TCP / IP | Yes | Yes | Yes | Yes | Yes | Yes | No | Yes | Yes | |||||
Static routing | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||||||
Dynamic DynDNS | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Access via RADIUS server | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
VPN: secure data communications; secure change of connection between LTE and LAN | Yes | Yes | Yes | Yes | Yes | No | Yes | Yes | |||||||
SSL installation | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
NTP server | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Alerts / Notifications | VT825t | VT855t | |||||||||||||
Alert types: E-mail, FTP log, Syslog, SMTP, SNMP Traps, SMS (Modem is ordered separately), Web-to-SMS, Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||||||
A maximum number of "mail to" recipients in an E-mail notification: | 50 | 20 | 20 | 20 | 10 | 20 | 20 | 20 | |||||||
A maximum number of "SMS to" recipients in an SMS notification: also the maximum amount of phone numbers | 50 | 20 | 20 | 20 | 1020 | 20 | 20 | ||||||||
Virtual sensors | VT825t | VT855t | |||||||||||||
PingsPings: Built-in function for server pinging. Test the reachability of a host in a network. Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||||||
IP cameras: Connect the IP MJPEG camera with a proxy via the master module. Only view, no record. | 4 | 4 | 4 | 4 | 4 | 4 | 4 | ||||||||
Get SNMP: Read data from external equipment via SNMP PDU GET (v1/2c) | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
User keys: Add users who have access using an RFID reader. | Yes | Yes | Yes | No | Yes | No | Yes | Yes | |||||||
Logic schemes: Used to specify automatic actions to events that occur in the system. Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||||||
Timers: Allows you to plan the events in the system. Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||||||
Triggers: Generate events in the system if logic is triggered. | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
SNMP traps | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Virtual Math element (combine several sensor data and calculate new data) | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Logic schemes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Modbus TCP/IP: read/write | Yes | Yes | Yes | Yes | Yes | No | Yes | Yes | |||||||
Power | VT825t | VT855t | |||||||||||||
Power input (230V AC): | x2 inputs option | x2 inputs option | x2 inputs option | No | No | No | x2 inputs option | x2 inputs option | |||||||
Power input (Power input (24 ÷ 48V DC): | x2 inputs option | x2 inputs option | x2 inputs option | No | No | No | x2 inputs option | x2 inputs option | |||||||
Power input (12V DC): | No | x1 input option | x1 input option | x2 inputs | x1 input | Inputx1 input option | x1 input option | ||||||||
Fuse: Fuse at the inlet | 1 A | 1 A | 1 A | 1 A | - | No1 A | 1 A | ||||||||
Min. power consumption: | 1 W | ||||||||||||||
Max. power consumption: | 30 W | 10 W | 10 W | 10 W | 12 W | 6 W | 8 W | 10 W | |||||||
The maximum current load on the relay: | 10А | 10А | 10А | 250mА | 250mА | 250mА10А | 10А | ||||||||
Redundant power supply: built-in voltage monitor, voltage range 9-12.6V. | Yes AC/DC DC/DC | Yes AC/DC DC/DC | Yes AC/DC DC/DC | Yes DC 12V | - | -Yes | |||||||||
Outputs | Yes AC/AC, AC/DC, DC/DC | Outputs | VT825t | VT855t | |||||||||||
Relay outputs: latching relays 240V*10A | 2 | 2 | 2 | - | - | - | 2 | 2 | |||||||
Relays outputs: 12V 0.25A 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | ||||||||
Max. dry contact outputs (contact closures/digital outputs) | 8 | 8- | - | - | - | -8 | |||||||||
Inputs | VT325tVT825t | VT855t | |||||||||||||
Analog port: 6P6C for connection of an analog sensor. (extendable using CAN bus) 8 built-in ports,up to 16 on the CAN bus extension unit | 8 built-in ports, | 8 built-in ports, | 6 8 built-in ports, | 4 built-in ports, | 8 6 built-in ports, | 4 built-in ports, | |||||||||
CAN port: Max number of sensors Use CAN-12V-1A for connecting more than 12 devices. | x1 port, max. 32 devices | x1 port, max. 32 devices | x1 port, max. 32 devices | x1 port, max. 32 devices | x1 port, max. 20 devices | x1 port, max. 10 devices | x1 port, max. 32 devices | x2 ports, max. 32 devices | |||||||
Dry contact inputs: (contact closures/digital inputs) Extadable using CAN bus and Dry contacts unit | 32 | 32 | 16 | 4 | 4 | 2 | 16 | 32 | |||||||
Modbus RTU (RS-485): Max. line length 1000m | 1 built-in port, up to 50 sensors | 1 built-in port, up to 50 sensors | - | - | 1 built-in port, up to 50 sensors | - | - | VT485m extension (Modbus or Reader), up to 50 sensors | |||||||
OSDP v2 reader extension: | - | - | - | - | - | - | coming soon | coming soon | |||||||
Video | VT825t | VT855t | |||||||||||||
AV camera | x1 | - | - | - | - | - | - | - | |||||||
USB cameras | x2 | x1 | x1 | x1 | x1 | x1 | x1 | x1 | |||||||
IP cameras | x4 | x4 | x4 | x4 | x4 | x4 | x4 | x4 | |||||||
RTSP IP camera | x1- | - | - | - | - | - | - | ||||||||
Other connectors | VT325tVT825t | VT855t | |||||||||||||
Ethernet port: 10/100Mbit | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
USB 2.0 Type A | 1 | 1 | 1 | - | - | - | - | - | |||||||
USB 2.0 micro 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | ||||||||
Switch Normal / Recovery: returns the device to factory settings | □Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||||||
External Memory / Logs | VT825t | VT855t | |||||||||||||
Micro SD card slot (SDXC up to 512 Gb) | Yes | Yes | Yes | Yes | No | 64Gb | Yes | Yes | |||||||
SD card formatting function (FAT32) | Yes | Yes | Yes | Yes | No | Yes | Yes | Yes | |||||||
USB flash drive: logs, sensor readings, item settings, etc. | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Send system log to e-mail: Logs, sensor data, elements settings, etc. | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Sensor dump files: save the per-second samples of analog and discrete sensors | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Syslog | Yes | Yes | ||||
Yes | Yes | Yes | Yes | Yes | Yes | ||||||||||
Send to FTP server: Logs, sensor data, elements settings, etc. | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Maximum amount of log files: 10,000 logs/days = 27 years Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||||||
Sample rate/period (logs, graphs) | 1 s | 1 s | 1 s | 1 s | 1 s | 1 s | 1 s | 1 s | |||||||
Modem (extension ordered separately) | VT825t | VT855t | |||||||||||||
4G LTE modem: ordered separately. | |||||||||||||||
Modem modes:
| Gateway / Access / SMS | Gateway / Access / SMS | Gateway / Access / SMS | Gateway / Access / SMS | Access / SMS | - | Gateway / Access / SMS | Gateway / Access / SMS | |||||||
Modem LED: STATUS | Yes | Yes | Yes | Yes | Yes | -Yes | Yes | ||||||||
Embedded onboard sensors | VT325tVT825t | VT855t | |||||||||||||
Temperature sensor: +/- 1 °C PCB temperature. | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Power supply voltage sensor: Accuracy (1%) | 1 | Main & Reserve | Main & Reserve | Main & Reserve | 1 | Yes | Main & Reserve | Main & Reserve | |||||||
LED indication | VT825t | VT855tVT325t | |||||||||||||
Ethernet LAN: LINK | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Ethernet LAN: ACT | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
CAN bus: STATUS | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
System: STATUS (ACT) | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
System: ERROR (ERR) | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
System: ALARM | - | Yes | Yes | - | Yes | Yes | Yes | Yes | |||||||
12V 0.25A outputs: STATUS (e.g. E1, E2) | x2 | x2 | x2 | x2 | x2 | x2 | x2 | x2 | |||||||
MODBUS RTU: STATUS | VT485M | VT485M | VT485M | VT485M | VT485M | - | - | - | |||||||
ODSP Reader. | VT485R | VT485R | VT485R | VT485R | VT485R- | - | Yes | ||||||||
NC/NO/COM Relay (e.g. R1, R2) | x2 | x2 | x2 | - | - | -x2 | x2 | ||||||||
HDD: Hard drive STATUS | Yes | - | - | - | - | - | - | - | |||||||
Environmental characteristics | VT325tVT825t | VT855t | |||||||||||||
Operating temperature: -10 to 80 °C | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Storage temperature: –25 to 85 °C | Yes | Yes °C | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Operating humidity: 0 to 90 %, non-condensing | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Storage humidity: 0 to 95 %, non-condensing Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||||||
Other Features | VT325tVT825t | VT855t | |||||||||||||
Installation: | 19” 1U | 19” 1U | 19” 1U | Desktop | DIN rail | Desktop | 19” 1U | 19” 1U | |||||||
Casing: | Sheet metal | Sheet metal | Sheet metal | Sheet metal | Plastic | PlasticSheet metal | Sheet metal | ||||||||
Dimensions (L x W x H) in mm: | 440x44x120 | 440x44x90 | 440x44x90 | 180x35x80 | 160x90x58 | 150x29x100 | 440x44x90 | 440x44x90 | |||||||
Weight: | 2 kg | 1,6 kg | 1,5 kg | 0,7 kg | 0,4 kg | 0,5 kg | 1,5 kg | 1,6 kg | |||||||
External chassis grounding: M4 thread | Yes | Yes | Yes | Yes | -Yes | Yes | Yes | ||||||||
Web interface (panels) | VT825t | VT855t | |||||||||||||
Dashboard panel: | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Overall statistics panel: | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
System tree panel: sensors and devices displayed in a hierarchy | Yes | Yes hierarchy | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Dry outputs panel: | Yes | Yes | Yes | No | Yes | Yes | Yes | Yes | |||||||
Dry inputs panel: | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Event log panel: amount of logs | 500 | 300 | 300 | 300 | 200 | 200 | 300 | 300 | |||||||
Logic schemes panel: | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Cameras panel: | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Map panel: 5 layers | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Users panel: | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
CAN configuration panel: | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
Graphs panel: Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||||||
Reset smoke detectors panel: Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||||||
Preferences panel: Web GUI, Network, Time, Logging, DynDNS, SNMP, RADIUS, FTP backup, VPN Clent, Modbus RTU, GPS, SMTP, Routing | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |||||||
System menu panel: About, Firmware, Export, Support Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | ||||||||
List of latest sent SMS messages: | 500 | 200 | 200 | 150 | 100 | 200 | 200 | 200 | |||||||
Analog sensor power reset: resets smoke sensors | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
● Built-in □ None ♦ Extension possible ◊ Not extendable