VT335i, VT336, VT825i, VT825ii, VT855i, VT855ii, VT960i, and VT960ii are the monitoring units and can not connect to each other. For scalability please use extension units and embedded boards.
...
Versions | VT335t (in development) | |||||||||
---|---|---|---|---|---|---|---|---|---|---|
Device Management: Web, SNMP, manually via SMS | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Sensor access: Three-level by login | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Interface | VT335t (in development) | |||||||||
LAN: Ethernet 10/100 Mbit | Yes | Yes | Yes | Yes | Yes | Yes | ||||
OS: Linux | v.5.10 | v.5.40 | v.5.40 | v.5.40 | v.3.10 | v.6.2 | ||||
Interface: Any browser | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Memory RAM: | 1Gb | 128Mb | 128Mb | 64Mb | 64Mb1 Gb | 128 Mb | 128 Mb | 64 Mb | 64 Mb | 128 Mb |
CPU speed: | 720 MHz | 720MHz600 MHz | 600MHz600 MHz | 600 MHz | 600MHz300 MHz300MHz | 720 MHz | ||||
Total CPU cores: | 4 | 1 | 1 | 1 | 1 | 2 | ||||
Clock: Built-in clock | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Timer: Built-in watchdog | Yes | Yes | Yes | Yes | Yes | Yes | ||||
The maximum amount of sensors: physical sensors, dry contacts, relays | 400 | 150 | 150 | 100 | 30 | |||||
The maximum amount of elements: notifications, triggers, timers, logic, sensors, dry contacts, SNMP Get, SNMP Trap, Dial task, and other elements | 2000 | 1000 | 1000 | 700 | 500 | |||||
Networking / Protocol support | VT335t (in development) | |||||||||
LTE Gateway mode: Internet access (routing for internal network) (modem ordered separately) | Yes | Yes | Yes | Yes | No | Yes | ||||
LTE Access mode: Internet access over LTE (modem ordered separately) | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Network protocols: DHCP; HTTP; HTTPS; SNMP v1, v2c, v3; SMTP; FTP; Syslog; TLS; | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Modbus RTU | Yes | Yes | No | No | Yes Modbus TCP / IP | VT485m extension | ||||
RS485 / OSDPv2: reader access control | No | No | No | No | No | VT485r extension | ||||
Modbus TCP / IP | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Static routing | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Dynamic DynDNS | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Access via RADIUS server | Yes | Yes | Yes | Yes | Yes | Yes | ||||
VPN: secure data communications; secure change of connection between LTE and LAN | Yes | Yes | Yes | Yes | Yes | Yes | ||||
SSL installation | Yes | Yes | Yes | Yes | Yes | Yes | ||||
NTP server | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Alerts / Notifications | VT335t (in development) | |||||||||
Alert types: E-mail, FTP log, Syslog, SMTP, SNMP Traps, SMS (Modem is ordered separately), Web-to-SMS, | Yes | Yes | Yes | Yes | Yes | Yes | ||||
A maximum number of "mail to" recipients in an E-mail notification: | 50 | 20 | 20 | 20 | 10 | |||||
A maximum number of "SMS to" recipients in an SMS notification: also the maximum amount of phone numbers | 50 | 20 | 20 | 20 | 10 | |||||
Virtual sensors | VT335t (in development) | |||||||||
Pings: Built-in function for server pinging. Test the reachability of a host in a network. | Yes | Yes | Yes | Yes | Yes | Yes | ||||
IP cameras: Connect the IP MJPEG camera with a proxy via the master module. Only view, no record. | 4 | 4 | 4 | 4 | 4 | |||||
Get SNMP: Read data from external equipment via SNMP PDU GET (v1/2c) | Yes | Yes | Yes | Yes | Yes | Yes | ||||
User keys: Add users who have access using an RFID reader. | Yes | Yes | Yes | No | Yes | |||||
Logic schemes: Used to specify automatic actions to events that occur in the system. | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Timers: Allows you to plan the events in the system. | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Triggers: Generate events in the system if logic is triggered. | Yes | Yes | Yes | Yes | Yes | Yes | ||||
SNMP traps | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Virtual Math element (combine several sensor data and calculate new data) | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Logic schemes | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Modbus TCP/IP: read/write | Yes | Yes | Yes | Yes | Yes | Yes | ||||
Power | VT335t (in development) | |||||||||
Power input: | 90-230V 230VAC | Options: 90-230V | 90-230V | 12V | 12V-230VAC, 12VDC, 24-48VDC | Options: 90-230VAC, 12VDC, 24-48VDC | x2 12VDC | 12VDC, optionally | 12VDC (custom order 24-48VDC) | |
Power input DC: | 24 ÷ 48V | 24 ÷ 48V | 24 ÷ 48V | 12V | □ | |||||
Fuse: Fuse at the inlet | 1A | 1A | 1A | 1A | □ | |||||
Max. power consumption: | 30W | 30W | 10W | 10W | 12W | |||||
The maximum current load on the relay: | 10А | 10А | 10А | 250mА | 250mА | |||||
Redundant power supply: built-in voltage monitor, voltage range 9-12.6V. | Yes AC/DC DC/DC | Yes AC/DC DC/DC | Yes AC/DC DC/DC | Yes DC 12V | □ | |||||
Outputs | ||||||||||
Relay outputs: latching relays 240V*10A | 2 | 2 | 2 | □ | □ | |||||
Relays outputs: 12V 0.25A | 2 | 2 | 2 | 2 | 2 | |||||
Max. dry contact outputs (contact closures/digital outputs) | 8 | 8 | □ | □ | □ | |||||
Audio output: AV OUT | 1 | □ | □ | □ | □ | |||||
Video output: AV OUT | 1 | □ | □ | □ | □ | |||||
Inputs | ||||||||||
Analog port: 6P6C for connection of an analog sensor. (extendable using CAN bus) | 8 built-in ports, | 8 built-in ports, | 8 built-in ports, | 4 built-in ports, | 6 built-in ports, | |||||
x1 CAN port: Max number of sensors Use CAN-12V-1A for connecting more than 12 devices. | 32 | 32 | 32 | 32 | 20 | |||||
Dry contact inputs: (contact closures/digital inputs) Extadable using CAN bus and Dry contacts unit | 32 built-in & extadable | 32 built-in & extadable | 16 built-in & extadable | 4 built-in & extadable | 4 built-in & extadable | |||||
Modbus RTU (RS-485): Max. line length 1000m | 1 built-in port, up to 50 sensors | 1 built-in port, up to 50 sensors | □ | □ | 1 built-in port, up to 50 sensors | |||||
Reader 1-Wire | 1 built-in port | 1 built-in port | □ | □ | □ | |||||
Video | ||||||||||
Video cameras: | AV, x2 USB, x4 IP | USB, x1 IP | USB, x1 IP | USB, x1 IP | USB, x1 IP | |||||
Video power supply: DC 12V 0,25A for analog camera | Yes | □ | □ | □ | □ | |||||
Other connectors | ||||||||||
Ethernet port: 10/100Mbit | Yes | Yes | Yes | Yes | Yes | |||||
USB 2.0 Type A | 1 | 1 | 1 | □ | □ | |||||
USB 2.0 micro | 1 | 1 | 1 | 1 | 1 | |||||
Switch Normal / Recovery: returns the device to factory settings | □ | Yes | Yes | Yes | Yes | |||||
FEL button: softly restarts the SATA drive | Yes | □ | □ | □ | □ | |||||
Shutdown button: Softly shuts down the device. | Yes | □ | □ | □ | □ | |||||
External Memory / Logs | ||||||||||
SD card slot (SDHC up to 32Gb) | Yes | Yes | Yes | Yes | No | |||||
SD card slot (SDXC up to 128Gb) | Yes | Yes | Yes | Yes | No | |||||
SD card formatting function (FAT32) | Yes | Yes | Yes | Yes | No | |||||
SATA Drive: 2.5" HDD or SSD (ordered separately) | Yes | No | No | No | No | |||||
USB flash drive: logs, sensor readings, item settings, etc. | Yes | Yes | Yes | Yes | Yes | |||||
Send system log to e-mail: Logs, sensor data, elements settings, etc. | Yes | Yes | Yes | Yes | Yes | |||||
Sensor dump files: save the per-second samples of analog and discrete sensors | Yes | Yes | Yes | Yes | Yes | |||||
Yes | Yes | Yes | Yes | Yes | ||||||
Send to FTP server: Logs, sensor data, elements settings, etc. | Yes | Yes | Yes | Yes | Yes | |||||
Maximum amount of log files: 10,000 logs/days = 27 years | Yes | Yes | Yes | Yes | Yes | |||||
Sample rate/period (logs, graphs) | 1 s | 1 s | 1 s | 1 s | 1 s | |||||
Extensions (modules are ordered separately) | ||||||||||
SATA: 2.5" HDD or SSD (ordered separately) | Yes | No | No | No | No | |||||
Modem (extension ordered separately) | ||||||||||
4G LTE modem: ordered separately. | ||||||||||
Modem modes:
| Gateway / Access / SMS | Gateway / Access / SMS | Gateway / Access / SMS | Gateway / Access / SMS | Access / SMS | |||||
Modem LED: STATUS | Yes | Yes | Yes | Yes | Yes | |||||
Embedded onboard sensors | ||||||||||
Temperature sensor: +/- 1 °C Case temperature. | Yes | Yes | Yes | Yes | Yes | |||||
Power supply voltage sensor: Accuracy (1%) | 1 | Main & Reserve | Main & Reserve | Main & Reserve | 1 | |||||
LED indication | ||||||||||
Ethernet LAN: LINK | Yes | Yes | Yes | Yes | Yes | |||||
Ethernet LAN: ACT | Yes | Yes | Yes | Yes | Yes | |||||
CAN bus: STATUS | Yes | Yes | Yes | Yes | Yes | |||||
System: STATUS (ACT) | Yes | Yes | Yes | Yes | Yes | |||||
System: ERROR (ERR) | Yes | Yes | Yes | Yes | Yes | |||||
System: ALARM | - | Yes | Yes | - | Yes | |||||
12V 0.25A outputs: STATUS (e.g. E1, E2) | x2 | x2 | x2 | x2 | x2 | |||||
MODBUS RTU: STATUS | - | - | - | - | x1 | |||||
TX: Modbus data sent activity (Transmission). | Yes | Yes | - | - | - | |||||
RX: Modbus data received activity (Receiving). | Yes | Yes | - | - | - | |||||
NC/NO/COM Relay (e.g. R1, R2) | x2 | x2 | x2 | - | - | |||||
HDD: Hard drive STATUS | Yes | - | - | - | - | |||||
Environmental characteristics | ||||||||||
Operating temperature: -10 to 80 °C | Yes | Yes | Yes | Yes | Yes | |||||
Storage temperature: –25 to 85 °C | Yes | Yes | Yes | Yes | Yes | |||||
Operating humidity: 0 to 90 %, non-condensing | Yes | Yes | Yes | Yes | Yes | |||||
Storage humidity: 0 to 95 %, non-condensing | Yes | Yes | Yes | Yes | Yes | |||||
Other Features | ||||||||||
Installation: | 19” 1U | 19” 1U | 19” 1U | Desktop | DIN rail | |||||
Dimensions (L x W x H) in mm: | 440*44*120 | 440*44*90 | 440*44*90 | 180*35*80 | 160*90*58 | |||||
Weight: | 2 kg | 1,5 kg | 1,5 kg | 0,7 kg | 0,4 kg | |||||
External chassis grounding: M4 thread | Yes | Yes | Yes | Yes | □ | |||||
Web interface (panels) | ||||||||||
Dashboard panel: | Yes | Yes | Yes | Yes | Yes | |||||
Overall statistics panel: | Yes | Yes | Yes | Yes | Yes | |||||
System tree panel: sensors and devices displayed in a hierarchy | Yes | Yes | Yes | Yes | Yes | |||||
Dry outputs panel: | Yes | Yes | Yes | No | Yes | |||||
Dry inputs panel: | Yes | Yes | Yes | Yes | Yes | |||||
Event log panel: amount of logs | 500 | 300 | 300 | 300 | 200 | |||||
Logic schemes panel: | Yes | Yes | Yes | Yes | Yes | |||||
Cameras panel: | Yes | Yes | Yes | Yes | Yes | |||||
Map panel: 5 layers | Yes | Yes | Yes | Yes | Yes | |||||
Users panel: | Yes | Yes | Yes | Yes | Yes | |||||
CAN configuration panel: | Yes | Yes | Yes | Yes | Yes | |||||
Graphs panel: | Yes | Yes | Yes | Yes | Yes | |||||
Reset smoke detectors panel: | Yes | Yes | Yes | Yes | Yes | |||||
Preferences panel: Web GUI, Network, Time, Logging, DynDNS, SNMP, RADIUS, FTP backup, VPN Clent, Modbus RTU, GPS, SMTP, Routing | ||||||||||
System menu panel: About, Firmware, Export, Support | Yes | Yes | Yes | Yes | Yes | |||||
List of latest sent SMS messages: | 500 | 200 | 200 | 150 | 100 | |||||
Analog sensor power reset: resets smoke sensors | Yes | Yes | Yes | Yes | Yes |
● Built-in □ None ♦ Extension possible ◊ Not extendable