Potential Problem | Possible Cause | Possible Solution |
---|---|---|
The data being displayed is inaccurate or not what you expect. | Incorrect setup values. | Check that You use the correct f(x) formula |
Incorrect voltage inputs. | Check power meter voltage input terminals to verify that adequate voltage is present | |
The power meter is wired improperly. | Check that all wires are connected correctly and that they are energized. See “Wiring Diagrams” of the device. | |
The sensor does not appear in the Vutlan monitoring interface | Communication lines are improperly connected. | Check the 6P4C RJ11 communication cable. |
The communication cable is inserted into the wrong port. | 6P4C RJ11 communication cable must be inserted into the analog port of the Vutlan monitoring system. | |
The sensor is always in alarm state. | The cable touches itself. | The cable can not touch itself. It needs to be straightened. Please check if the cable is bent anywhere. |
The cable is twisted or pressed down too much. | Do not twist or press down the cable too much. This may lead to deformation. The cable has two sensing wires, these wires can not touch each other. | |
The cable is located on a conductive surface. | Do not put the cable on a conductive surface. |
...