Function and purpose

Info

Notice on 6th June 2019: The product has been altered. RJ9 4P2C connected is now used instead of 2P Power Terminal.

...

"WLC / Water leak cable" is ordered separately!  When water is in contact with the detection cable sensor indicates the emergence of moisture. The whole area can be effectively monitored by placing the cable near or along with possible flood sources.

Dimensions


Usage examples

Technical specifications


VT591 / Water leak sensor specifications
Dimensions60×18×18 mm
Weight60 g
Input

2 wire (WDC cable)

OutputRJ11 / RJ12 (6p4c)
Operating temperature-10 °C to +80 °C
Operating humidity5% to 95% (Non-Condensing)
MountingMounting bracket included.
Power consumption60mW
Max. distance m100 m
HS Code9025 80 400
ComponentsManufactured in E.U.
Special featuresResponse time: 15 sec., Recovery time: Depends on how fast the sensor dries out


WLC / Water leak cable specifications

DescriptionWLC can work in high humidity, pollution, and hazardous waste
Detectable liquidsClean, polluted & distilled water; acids; alkalis; alcohols, and other electrically conductive liquid
Diameter5.5 mm in diameter
Lengths

Order options include 10m, 15m, 25m, 50m, or custom length.

Weight

26 g/m

Operating humidity0° - 95 %
Max. cable length225 m
Inputsx2 wires

Package content

Include Page
VT591 and WLC package content
VT591 and WLC package content

Connecting WLC / Water leak cable

Warning

The cable can not touch itself. It needs to be straightened.

...

  1. Connect the "VT591 / Water leak sensor" to the monitoring unit. The connection is plug-an-play.
  2. Connect the "VTC / Terminal cable" to the VT591 sensor.
  3. Connect "WLC / Water detection cable" to "VTC / Terminal cable".
  4. Connect any additional "WLC / Water detection cables" to each other as shown in the picture above to make a chain connection.
  5. Wire the WLC rope around or under potentially leaking objects around the perimeter or under the raised floors.
  6. Put a protective cap on the connector of the last WLC cable in a chain.
  7. The sensor is ready to use.

Analog sensor connection

Include Page
Analog sensors connection
Analog sensors connection

Installation examples

Please find installation examples in our articles "Water leakage detection using cable sensor and spot sensor" and "Leak detection under raised floors in data centers".

Cable pinouts

The sensor uses a standard Vutlan analog sensor cable(RJ11/RJ12 to RJ11/RJ12) for connecting to the monitoring unit. You can find further instructions at: Analog sensors connection

Technical support

The device does not contain any user-serviceable parts. If the power meter requires service, contact your local sales representative. Do not open the device. Opening the device voids the warranty.

Schematics

You can change the R10 resistor using the following schemes.

Image Modified

Image Modified

Troubleshooting

The following table describes potential problems and their possible causes. It also describes checks you can perform or possible solutions for each. After referring to this table, if you cannot resolve the problem, contact your local Vutlan sales representative for assistance.

...