The sensor must be used together with

Image Removed
Image Added

WLC / Water leak cable

(recommended)

(ordered separately)

"WLC / Water leak cable" is ordered separately!  When water is in contact with the detection cable sensor indicates the emergence of moisture. The whole area can be effectively monitored by placing the cable near or along with possible flood sources.

Dimensions

...

Usage examples

...

Technical specifications

VT591 / Water leak sensor specifications

Dimensions

60×18×18 mm

Weight

60 g

Input

2 wire (WDC cable)

Output

RJ11 / RJ12 (6p4c)

Operating temperature

-10 °C to +80 °C

Operating humidity

5% to 95% (Non-Condensing)

Mounting

Mounting bracket included.

Power consumption

60mW

Max. distance m

100 m

HS Code

9025 80 400

Components

Manufactured in E.U.

Special features

Response time: 15 sec., Recovery time: Depends on how fast the sensor dries out


WLC / Water leak cable specifications

Description

WLC can work in high humidity, pollution, and hazardous waste

Detectable liquids

Clean, polluted & distilled water; acids; alkalis; alcohols, and other electrically conductive liquid

Diameter

5.5 mm in diameter

Lengths

Order options include 10m, 15m, 25m, 50m, or custom length.

Weight

26 g/m

Operating humidity

0° - 95 %

Max. cable length

225 m

Inputs

x2 wires

Package content

Include Page
VT591 and WLC package content
VT591 and WLC package content

Connecting WLC / Water leak cable

...

Warning

The cable can not touch itself. It needs to be straightened.

...

Warning

You can cut the cable, but you need to isolate the ends so that they do not touch each other. And do not loop the cable.

  1. Connect the "VT591 / Water leak sensor" to the monitoring unit. The connection is plug-an-play.

  2. Connect the "VTC / Terminal cable" to the VT591 sensor.

  3. Connect "WLC / Water detection cable" to "VTC / Terminal cable".

  4. Connect any additional "WLC / Water detection cables" to each other as shown in the picture above to make a chain connection.

  5. Wire the WLC rope around or under potentially leaking objects around the perimeter or under the raised floors.

  6. Put a protective cap on the connector of the last WLC cable in a chain.

  7. The sensor is ready to use.

Analog sensor connection

Include Page
Analog sensors connection
Analog sensors connection

Installation examples

Please find installation examples in our articles "Water leakage detection using cable sensor and spot sensor" and "Leak detection under raised floors in data centers".

...

The sensor uses a standard Vutlan analog sensor cable(RJ11/RJ12 to RJ11/RJ12) for connecting to the monitoring unit. You can find further instructions at : the Analog sensors connection

Technical support

The device does not contain any user-serviceable parts. If the power meter requires service, contact your local sales representative. Do not open the device. Opening the device voids the warranty.

Schematics

You can change the R10 resistor using the following schemes.

Image Removed

...

Troubleshooting

The following table describes potential problems and their possible causes. It also describes checks you can perform or possible solutions for each. After referring to this table, if you cannot resolve the problem, contact your local Vutlan sales representative for assistance.


Potential Problem

Possible Cause

Possible Solution

The data being displayed is inaccurate or not what you expect.

Incorrect setup values.

Check that You use the correct f(x) formula

Incorrect voltage inputs.

Check power meter voltage input terminals to verify that adequate voltage is present

The power meter is wired improperly.

Check that all wires are connected correctly and that they are energized. See “Wiring Diagrams” of the device.

The sensor does not appear in the Vutlan monitoring interface

Communication lines are improperly connected.

Check the 6P4C RJ11 communication cable.

The communication cable is inserted into the wrong port.

6P4C RJ11 communication cable must be inserted into the analog port of the Vutlan monitoring system.

...