Documentation page: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/35127335/VT440+Dry+contacts+unit
Product page VT440: https://vutlan.com/can-sensors/24-vt440-dry-contacts-unit.html
Product page VT32: https://vutlan.com/contacts/9-vt32-dry-contacts-board.html
Order options
VT440 can be ordered in two options:
...
b) VT440 + VT32 (x64 dry contact inputs)
Function and purpose
Allows increasing the number of dry contact inputs connected to any Vutlan monitoring unit. Adds 32 dry contacts. Can be connected to any CAN port on a CAN bus chain. Can be chained with other CAN sensors.
The number of dry contacts inside VT440 can be increased up to 64 with an extension module "VT32 / dry contacts module".
Physical description
1. "1...32" - Dry contacts terminal.
...
Note |
---|
Do not use the DIP switch "FR" labeled "1", it should always be OFF. If this switch is turned ON, the module will turn off. This switch is only needed for programming purposes |
Technical specifications
Feature | Description |
---|---|
Type | CAN sensor |
Network interface | CAN open |
Usage | Adds x32 dry contact inputs (digital inputs) |
Product dimensions | (Width, Height, Depth) 215 x 40 x 40 mm |
Power Consumption | 1 Watt |
Operating temperature | Optimal temperature range: -10° C to +80° C Extended temperature range: -40° С to +100° C |
Mounting possibilities | 19" rack-mountable Desktop Wall mount |
Max. distance from the unit | 225 m |
Input terminals | Dry contacts / Digital inputs: 32 contacts RJ-12 ports: x2 |
Expansions (ordered separately) | "VT32 / Dry contacts board" - adds additional x32 contacts |
Status Indicators | Red / Green Led |
Operating humidity | 0 to 95 % |
Storage temperature | -40° С to +100° C |
Storage humidity | 0 to 95 % |
Manufactured in (country) | Manufactured in Slovak Republic, E.U. |
HS Code | 8471 50 000 |
Daisy chain | Yes, possible |
Package includes
Include Page | ||||
---|---|---|---|---|
|
Drawing
Installation
"TR" - is the nearest switch to CAN inputs. This switch should be turned "ON" on the last sensor in the CAN chain. The last sensor in the long chain with a length of more than 10 meters, the terminator should be in "OFF" position.
pic.2.1: TR is ON, FR is OFF. pic.2.2: TR is OFF, FR is OFF.
CAN devices connection
Include Page | ||||
---|---|---|---|---|
|
Setting up CAN
Include Page | ||||
---|---|---|---|---|
|
...