Documentation page: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/93421575/VT590+Leak+sensor
Product page: https://vutlan.com/analog-sensors/22-vt590-spot-water-detector.html
Function and purpose
For the installation at the bottom of IT racks and cabinets; at the bottom of raised floors; at the bottom of trays and under equipment that can potentially leak. When water is in contact with both metal cores, the sensor indicates the emergence of moisture.
Attention! Metal cores are detectors of water, mount strictly downwards as close as possible to a floor.
Technical specifications
Communications | Description |
---|---|
Sensor type: | Analog sensor |
Outputs: | x1 RJ11 6P4C port |
Daisy chain? | No |
Max. distance from the monitoring unit: | 100 m |
Environmental | |
Operating temperature: | Min. -10 °C - Max.80 °C |
Operating humidity: | 5 to 95% (Non-Condensing) |
Power requirements | |
Power consumption | 60mW |
Mechanics | |
Dimensions: | 60×18×18 mm |
Mounting: | Mounting bracket included. Installed at the bottom of racks or floors or trays. |
Packaging weight: | 125 g |
Cable length: | 3m |
General | |
Manufactured in: | Slovak Republic, European Union |
Manufactured by: | Vutlan s.r.o. |
HS Code: | 9025 80 400 |
Warranty: | 90 days |
Package includes
Include Page | ||||
---|---|---|---|---|
|
Drawings
View file | ||||
---|---|---|---|---|
|
View file | ||||
---|---|---|---|---|
|
Connecting the leak sensor
The sensor uses a standard Vutlan analog sensor cable for connecting to the monitoring unit. You can find further instructions at: Analog sensors connection
Installation using a sticker and a bracket
1) There's a round bump at the bottom of the plastic enclosure of the sensor. It is used for fastening when the sensor is mounted together with the on walls using a screw. In the current example, it is not needed. If you are planning to mount a device differently, do not follow this step.
...
4) The sensor is mounted.
Installation examples
Please find installation examples in our article "Water leakage detection using cable sensor and spot sensor" https://vutlan.com/blog/post/leakage-detection.html.
Connecting analog sensors
The sensor uses a standard Vutlan analog sensor cable for connecting to the monitoring unit.
Include Page | ||||
---|---|---|---|---|
|
Configure analog sensors
Include Page | ||||
---|---|---|---|---|
|
API: managing system elements by 3rd party Software
Vutlan has an open API. Read more at:
...