Package content
Include Page | ||||
---|---|---|---|---|
|
Connecting WDC / Water detection rope
...
Warning |
---|
Do not put the cable on a conductive surface. |
Warning |
---|
You can cut the cable, but you need to isolate the ends so that they do not touch each other. And do not loop the cable. |
- Connect the "VT591 / Water leak sensor" to the monitoring unit. The connection is plug-an-play.
- Connect "VTC / Terminal cable" to the VT591 sensor.
- Connect "WLC / Water detection cable" to "VTC / Terminal cable".
- Connect any additional "WLC / Water detection cables" to each other as shown in the picture above to make a chain connection.
- Wire the WLC rope around or under potentially leaking objects around the perimeter or under raised floors.
- Put a protective cap on the connector of the last WLC cable in a chain.
- The sensor is ready to use.
...