Notice on 6th June 2019: The product has been altered. RJ9 4P2C connected is now used instead of 2P Power Terminal.


Sensor The sensor must be used together with

...

When water is in contact with the detection cable sensor indicates the emergence of moisture. "WDC / Water detection rope" and "WLC / Water leakage cable" are ordered separately! The whole area can be effectively monitored by placing the cable near or along with possible flood sources.

Dimensions

...


VT591 / Water leak sensor specifications
Dimensions60×18×18 mm
Weight60 g
Input

2 wire (WDC cable)

OutputRJ11 / RJ12 (6p4c)
Operating temperatureTemperature : Min. -10 °C - Max.to +80 °C
Operating humidityHumidity : Min. 5% - Max. 5% to 95% (Non-Condensing)
MountingMounting bracket included.
Power consumption60mW
Max. distance m100 m
HS Code9025 80 400
ComponentsManufactured in E.U.
Special featuresResponse time: 15 sec., Recovery time: Depends on how fast the sensor dries out


WDC / Water detection rope specifications

DescriptionWDC can detect moisture (works until the dew point) and does not welcome pollution!
Detectable liquidsClean, polluted & distilled water; acids; alkalis; alcohols, and other electrically conductive liquid
Diameter3 mm in diameter
Lengths

Order options include 6m, 10m, 17m, 25m, 50m, or custom length.

Weight

15 g/m

Operating temperatureMin. -50° C, Max. 105° C
Max. rope length225 m
Conductor27% Ni

...

WLC / Water leak cable specifications

DescriptionWLC can work in high humidity, pollution, and hazardous waste
Detectable liquidsClean, polluted & distilled water; acids; alkalis; alcohols, and other electrically conductive liquid
Diameter5.5 mm in diameter
Lengths

Order options include 10m, 15m, 25m, 50m, or custom length.

Weight

26 g/m

Operating humidity0° - 100 %
Max. cable length225 m
Inputsx2 wires

Package content

Include Page
VT591, WDC, WLC package content
VT591, WDC, WLC package content

...

Connecting WDC / Water detection rope

  1. Connect the WDC rope sensor to the VT591 leak sensor.
  2. Wire the WDC rope around or under potentially leaking objects around the perimeter or under raised floors.
  3. Cconnect Connect the sensor to the monitoring unit. Connection The connection is plug-an-play.
  4. Sensor The sensor is ready to use.

Connecting WLC / Water leak cable

...

  1. Connect the "VT591 / Water leak sensor" to the monitoring unit. Connection The connection is plug-an-play.
  2. Connect "VTC / Terminal cable" to the VT591 sensor.
  3. Connect "WLC / Water detection cable" to "VTC / Terminal cable".
  4. Connect any additional "WLC / Water detection cables" to each other as shown on in the picture above to make a chain connection.
  5. Wire the WLC rope around or under potentially leaking objects around the perimeter or under raised floors.
  6. Put a protective cap on the connector of the last WLC cable in a chain.
  7. Sensor The sensor is ready to use.

Analog sensor connection

Include Page
Analog sensors connection
Analog sensors connection

...

Please find installation examples in our article "Water leakage detection using cable sensor and spot sensor".

Cable pinouts

Sensor The sensor uses a standard Vutlan analog sensor cable(RJ11/RJ12 to RJ11/RJ12) for connecting to the monitoring unit. You can find further instructions at: Analog sensors connection

...

The following table describes potential problems and their possible causes. It also describes checks you can perform or possible solutions for each. After referring to this table, if you cannot resolve the problem, contact the your local Vutlan sales representative for assistance.


Potential ProblemPossible CausePossible Solution
The data being displayed is inaccurate or not what you expect.

Incorrect setup values.Check that You use the correct f(x) formula
Incorrect voltage inputs.Check power meter voltage input terminals to verify that adequate voltage is present
Power
The power meter is wired improperly.Check that all wires are connected correctly and that they are energized. See “Wiring Diagrams” of the device.
Sensor
The sensor does not appear in the Vutlan monitoring interface
Communications
Communication lines are improperly connected.Check 6P4C RJ11 communication cable.
Communication
The communication cable is inserted
in to a
into the wrong port.6P4C RJ11 communication cable must be inserted into the analog port of the Vutlan monitoring system.