VT424 DC Millivoltmeter

VT424 DC Millivoltmeter

Product page: https://www.vutlan.com/home/59-vt424-dc-voltage-monitor.html

Datasheet page: VT424 DC Millivoltmeter

Package includes: VT424 package content

Functional description & components

 

 

Function & Order options

The Millivoltmeter is a device designed for the measurement of very small DC voltage, converting the data into a format compatible with a Vutlan monitoring system. It allows for real-time remote monitoring of DC voltage levels in various applications, such as data centers, industrial automation, and renewable energy systems.

VT424 is an analog plug-and-play sensor and can be connected to any analog port of Vutlan monitoring system.

The maximum number of VT424 sensors connected to a Vutlan monitoring system and the maximum cable length can be extended using the "VT408 / Sensor extension unit".

 

Models

VT424 : measured voltage 0-24mV, the better measurement for low voltages.

Can be produced in any other ranges as a custom order.

 

Technical specifications

Function & purpose

Description

Function & purpose

Description

Type

Analog, plug-and-play

Measures

DC voltage

Possible options

0-100mV

Measured voltage

24mV

Accuracy

1%

K coefficient

~100, used inside the interface

 

Communications

Description

Daisy chain

No

Input

3-pin terminal, pitch 2.54mm

Output

RJ11, 6p4c

Cable length

2m

Max. distance

50 m from Vutlan monitoring system or VT408 extension unit

 

Environmental

Description

Operating temperature

from -10° C to +80° C

Operating humidity

from 5% to 95% (Non-Condensing)

 

Mechanical

Description

Mounting

Desktop, Wall mount

Dimensions

80 × 19 × 19.5 mm (LxWxH)

Weight

15 g

 

Power

Description

Power Consumption

1 mW

 

General

Description

Origin:

Made in EU

HS Code

9030 33 100

GTIN

8588009886846

Warranty:

90 days

 

Use cases

Here are some use cases for the VT424 DC monitor:

 

Drawing

 

 

Installation

1. Connect one end of RJ11 cable to any Vutlan monitoring unit's analog port A1-A8 and the other end to the VT424 / DC Voltage Monitor.

2. Connect "+" and "-" to the 3P terminal.

3. Insert the terminal into VT424.

 