VT604 / Switched PDU v1.2 (legacy)

1. "GSM ANTENNA" - connector, used when the GSM modem is installed inside of the appliance to connect the GSM antenna. (GSM modem is ordered separately)

2. LEDs: "OUTLETS 1 - 8" - orange - indicate outlet status.

3. LEDs:

    "ACT / STATUS" - Green - indicates appliance status

    "E1" - green - indicates 12V E1 relay status

    "E2" - green - indicates 12V E2 relay status

    "CAN" - Green - indicates CAN bus status; "CAN" blinks slowly - nothing is connected; "CAN" blinks fast - configuration is in the process; "CAN" glows constantly - connected to CAN devices

4a. "GSM status" - indicates GSM SIM card status. Blinking = working. (VT00 / GSM modem is ordered separately);

4b. "SIM" - connector with an ejector, used when VT700 / GSM modem is installed inside of the appliance to connect SIM card (VT700 / GSM modem is ordered separately).

5. "USB" - type miniAB USB-port 2.0, required to connect a USB camera or to restore an appliance.

6. LED: "ERROR» - red - indicates error and traffic.

  •  the operating mode of the device: the norm is extinguished, not the norm - a constant glow;

  •  software update mode: switches at a rate of 2 times per second;

7. "RESTART" or "RESET" - restarts the appliance.

8. "LAN" - Ethernet 10/100 Base-T port, provides an Ethernet connection.

• LEDs - "yellow" (status) and "green" (traffic) show the network traffic. The status LED: flashes green when the system starts up, and shows the connection state (constant green light - the connection is established, blinking green - the connection attempt).

9. "CAN" - digital connector RJ12 for the connection of CAN sensors and CAN extensions on a CAN bus, with auto-sensing.

10. "A1..A2" - 2 RJ12 analog sensor inputs with auto-sensing.

11. "" - External chassis grounding, M4 thread.

12. "FUSE" - 10A. 5х20 мм.

13. INPUTS "AC1" C14 240V 10A

14. 4x power "OUTLETS" C13

15. "Dip switch" Normal ↑ Off - the system should be always switched to this mode.

Recovery ↓ On - use this option only in case you need to recover manufacturing settings.

16. "OUTPUT 12V 0.25A" - 12V 0.25A output electronic relay terminal

17. "DRY CONTACTS 1...2" - Dry contacts terminal (type IN)

18. "TEMPERATURE SENSOR" - Accuracy +/- 1 °C.