Functional description & components

Function

At installation indoors, inside the rack, etc., the sensor monitors the occurrence of smoke inside the building. It is a daisy chain sensor, max. distance from the monitoring unit is 150 meters.

The maximum amount of sensors and maximum length can be extended using the "VT408 / Sensor extension unit".

Components

The smoke sensor consists of a compact plastic housing with ventilation holes.

The sensor can not be used on its own. It must be used together with Vutlan monitoring systems.

Technical specifications

Feature
Description

Type

Analog

Dimensions

Ø100×45 mm

Sensor weight

150 g

Packaging weight

290 g

Inputs

x2 ports RJ12

Operating temperature

Optimal: -10 °C to +55° C

Extended: -10 °C to +80° C

Operating humidity

5% to 95% (Non-Condensing)

Average lifespan

>=10 years

Storage temperature

-10 °C to +55° C

Storage humidity

5% to 95% (Non-Condensing)

Power consumption

100 mW

Status Indicators

Red LED

Max. distance m

150 m

HS Code

8531 10 950

Components

Manufactured in E.U.

Daisy chain

Yes, sensors can be connected in a chain. The system will show all daisy chain sensors in one chain as one sensor.

Mounting

On the сeiling

Drawing

Package content

Safety instructions

Siting location requirements

To ensure the proper functioning of the unit, the conditions for the installation site of the unit specified in section “Technical specifications” must be observed.

Electromagnetic interference

Interfering electrical installations (high frequency) should be avoided.

Installation procedure

Notes on assembly

Installation with the mounting plate provided

The smoke alarm is installed using the mounting plate provided.

Connecting the smoke sensor

Connect one end of the RJ11 / RJ12 cable to the monitoring unit and the other end to any of the two inputs of the smoke sensor. It is possible to connect up to 10 sensors to one analog port. To do so connect the new RJ11 cable to a free input of the already connected smoke sensor and the other end to the next smoke sensor in a chain. See the picture below. RJ11 or RJ12 cable pinouts can be found in the picture below. After the system will start and sense the smoke detector, the LED on the smoke detector will blink dimly once a second.

Testing the smoke sensors

During system operation, take a needle or paper clip and insert it into the hole on the cover of the sensor, try to move it there until the blinking dimly LED will flash brightly. That means that sensor is in a good state. After inspection, return the sensor /s to a normal state. To do this, either disconnect them from the system, or in a system interface, go to the smoke sensors tab, and restart them.

Connecting analog sensors

Article link: Analog sensors connection

Analog sensor configuration

Article link: Sensor configuration