Reading Elements

The read element request contains the following fields:


Example of a response to a query for a specific element:


<elementid="302001"module="2013"clas="switch"type="outlet"name="Outlet-1"state="off"value="0"initial="off"pulse="1"hwport="1"></element>


Example of a response to a query for a list of all elements:

<elements>
    <elementid="201001"module="2005"num="-1"clas="analog"type="temperature"name="Onboard Temperature"state="normal"value="24.40"view="0"um="°C"></element>
    <elementid="301001"module="2006"num="-1"clas="switch"type="relay"name="Analog Power"state="on"value="1"view="0"></element>
</elements>


The elements in the monitoring system have the following common attributes:


Possible classes and types of elements:


The set of states in which an element may reside depends on its class:

Status\Classdiscreteanalogswitchdevhwr (1)devirt (1)notifierDescription
unknown





the system can not determine the state of the element, under normal circumstances such an element is not available
unreal





error state of the element, under normal conditions does not occur, system error
not connected******element is not connected
low alarm
*
**
Element parameters exceed the lower alarm threshold
low warning
*
**
Element parameters are below the norm
normal**
**
the element is in the normal state
high warning
*
**
Element parameters above normal
high alarm
*
**
Element parameters exceed the upper alarm threshold
warning


**
Element parameters above normal
alarm*

**
the item is in alarm state
on

****the element is always in the active (on) state
off

****the element is constantly in the passive (off) state
pulse

****The element is temporarily in a state opposite to its constant state

(1) - the possible state depends on the type of device.




Sensors in the Vutlan monitoring system

Sensors with a discrete output (clas = discrete)

Possible states: not connected, normal, alarm

Range of possible values: 0, 1

Parameters (attributes):

If the element does return any one of the attribute from the specified - then the value of this attribute is not determined in the process of work and its installation does not affect the operation of the element.

Elements with a discrete output can also have other attributes.

TypeIconNameAnalog / Built-in / SC408CAN-modules (amount of sensors of this type)Notes
dry
Dry contact
VT16 / Dry contacts board
VT32 / Dry contacts board
VT440 / Dry contacts unit  (16/32/48/64)
VT430 / Rack control unit

door
Access sensorSC530 / Access sensor
VT430 / Rack control unit

airflow
Airflow sensor-

SC450 Aiflow sensor (8)


motion
PIR sensor
VT570 / PIR sensor

VT470 / PIR, vibration and temperature sensor

vibration
Vibration sensorSC541 / Vibration sensor
VT470 / PIR, vibration and temperature sensor

smoke
Smoke sensor
VT560 / Smoke detector
VT460 / Smoke, humidity and temperature sensor



water
Leakage sensor
VT590 / Spot water detector
VT591 / Water leak sensor
-
button
Button--PDUs

Sensors with analog output (clas = analog)

Possible states: not connected, low alarm, low warning, normal, high warning, high alarm

Parameters (attributes):

If the element does not return any attribute from the specified - then the value of this attribute is not determined in the process of work and its installation does not affect the operation of the element.

Elements with an analog output can also have other attributes.

TypeIconNameAnalog / Built-in / SC408CAN-modulesNotes
temperature
Temperature sensor
VT500 / Temperature sensor
VT460 / Smoke, humidity and temperature sensor
VT470 / PIR, vibration and temperature sensor
встроенный датчик температуры на материнской плате
humidity
Humidty sensor
VT510 / Humidity sensor
VT460 / Smoke, humidity and temperature sensor
VT430 / Rack control unit

voltage
Voltage sensor
VT520 / AC voltage monitor
-встроенный датчик напряжения на материнской плате
fvoltage
DC voltage monitor
VT410 / DC voltage monitor
-
current
Измерительный датчик тока--распределители питания
fcurrent
Преобразовательный датчик тока
VT420 / Converter 4-20mA
-
vibration
Vibration sensorSC540 vibration sensor-
power
Power sensor--распределители питания
factor
Ratio of the ratio coefficients--распределители питания
frequency
Frequency Sensor--распределители питания

Switches (clas=switch)

Possible states: not connected, on, off, pulse

Type

Icon

Name

Notes

relay
Relay

SC8100 (4)

1-Wire power management,
power management of the analog module and VT408

outlet
Outlet

SC8110 (4)

SC1108 (8)

toggle
Toggle switchSC32xx (АВР)

Devices (clas=devhwr)

Possible states: not connected, normal, alarm

Type

Icon

Name

Notes

reader
iButton reader
ip-cam
IP camera
usb-cam
USB camera
GSM modem
GSM modem

Virtual elements (clas=devirt)

Possible states: not connected, normal, alarm

Feature: created in the system by the user

Type

Icon

Name

Notes

timer
Timer
ping
Ping
logic
Logic scheme
trigger
Trigger

Notifiers (clas=notifier)

Possible states: normal

Feature: are created in the system by the user, activated by the logic schemes

Type

Icon

Name

Notes

mailer
E-mail notification
snmp trap
Trap PDU
sms
SMS


Further reading: