The read element request contains the following fields:
Example of a response to a query for a specific element:
<elementid="302001"module="2013"clas="switch"type="outlet"name="Outlet-1"state="off"value="0"initial="off"pulse="1"hwport="1"></element> |
Example of a response to a query for a list of all elements:
<elements> <elementid="201001"module="2005"num="-1"clas="analog"type="temperature"name="Onboard Temperature"state="normal"value="24.40"view="0"um="°C"></element> <elementid="301001"module="2006"num="-1"clas="switch"type="relay"name="Analog Power"state="on"value="1"view="0"></element> |
The elements in the monitoring system have the following common attributes:
Possible classes and types of elements:
The set of states in which an element may reside depends on its class:
Status\Class | discrete | analog | switch | devhwr (1) | devirt (1) | notifier | Description |
---|---|---|---|---|---|---|---|
unknown | the system can not determine the state of the element, under normal circumstances such an element is not available | ||||||
unreal | error state of the element, under normal conditions does not occur, system error | ||||||
not connected | * | * | * | * | * | * | element is not connected |
low alarm | * | * | * | Element parameters exceed the lower alarm threshold | |||
low warning | * | * | * | Element parameters are below the norm | |||
normal | * | * | * | * | the element is in the normal state | ||
high warning | * | * | * | Element parameters above normal | |||
high alarm | * | * | * | Element parameters exceed the upper alarm threshold | |||
warning | * | * | Element parameters above normal | ||||
alarm | * | * | * | the item is in alarm state | |||
on | * | * | * | * | the element is always in the active (on) state | ||
off | * | * | * | * | the element is constantly in the passive (off) state | ||
pulse | * | * | * | * | The element is temporarily in a state opposite to its constant state |
(1) - the possible state depends on the type of device.
Possible states: not connected, normal, alarm
Range of possible values: 0, 1
Parameters (attributes):
If the element does return any one of the attribute from the specified - then the value of this attribute is not determined in the process of work and its installation does not affect the operation of the element.
Elements with a discrete output can also have other attributes.
Type | Icon | Name | Analog / Built-in / SC408 | CAN-modules (amount of sensors of this type) | Notes |
---|---|---|---|---|---|
dry | Dry contact | VT16 / Dry contacts boardVT32 / Dry contacts board | VT440 / Dry contacts unit (16/32/48/64)VT430 / Rack control unit | ||
door | Access sensor | SC530 / Access sensor | VT430 / Rack control unit | ||
airflow | Airflow sensor | - | SC450 Aiflow sensor (8) | ||
motion | PIR sensor | VT570 / PIR sensor | VT470 / PIR, vibration and temperature sensor | ||
vibration | Vibration sensor | SC541 / Vibration sensor | VT470 / PIR, vibration and temperature sensor | ||
smoke | Smoke sensor | VT560 / Smoke detector | VT460 / Smoke, humidity and temperature sensor | ||
water | Leakage sensor | VT590 / Spot water detectorVT591 / Water leak sensor | - | ||
button | Button | - | - | PDUs |
Possible states: not connected, low alarm, low warning, normal, high warning, high alarm
Parameters (attributes):
If the element does not return any attribute from the specified - then the value of this attribute is not determined in the process of work and its installation does not affect the operation of the element.
Elements with an analog output can also have other attributes.
Type | Icon | Name | Analog / Built-in / SC408 | CAN-modules | Notes |
---|---|---|---|---|---|
temperature | Temperature sensor | VT500 / Temperature sensor | VT460 / Smoke, humidity and temperature sensorVT470 / PIR, vibration and temperature sensor | встроенный датчик температуры на материнской плате | |
humidity | Humidty sensor | VT510 / Humidity sensor | VT460 / Smoke, humidity and temperature sensorVT430 / Rack control unit | ||
voltage | Voltage sensor | VT520 / AC voltage monitor | - | встроенный датчик напряжения на материнской плате | |
fvoltage | DC voltage monitor | VT410 / DC voltage monitor | - | ||
current | Измерительный датчик тока | - | - | распределители питания | |
fcurrent | Преобразовательный датчик тока | VT420 / Converter 4-20mA | - | ||
vibration | Vibration sensor | SC540 vibration sensor | - | ||
power | Power sensor | - | - | распределители питания | |
factor | Ratio of the ratio coefficients | - | - | распределители питания | |
frequency | Frequency Sensor | - | - | распределители питания |
Possible states: not connected, on, off, pulse
Type | Icon | Name | Notes |
---|---|---|---|
relay | Relay | SC8100 (4) 1-Wire power management, | |
outlet | Outlet | SC8110 (4) SC1108 (8) | |
toggle | Toggle switch | SC32xx (АВР) |
Possible states: not connected, normal, alarm
Type | Icon | Name | Notes |
---|---|---|---|
reader | iButton reader | ||
ip-cam | IP camera | ||
usb-cam | USB camera | ||
GSM modem | GSM modem |
Possible states: not connected, normal, alarm
Feature: created in the system by the user
Type | Icon | Name | Notes |
---|---|---|---|
timer | Timer | ||
ping | Ping | ||
logic | Logic scheme | ||
trigger | Trigger |
Possible states: normal
Feature: are created in the system by the user, activated by the logic schemes
Type | Icon | Name | Notes |
---|---|---|---|
mailer | E-mail notification | ||
snmp trap | Trap PDU | ||
sms | SMS |
Further reading: