Product page: https://vutlan.com/can-sensors/27-vt460-smoke-humidity-and-temperature-sensor.html
From the picture above:
The sensor can not be used on its own. It must be used together with Vutlan monitoring systems. |
The sensor is installed using the mounting plate provided.
Connect one end of the RJ11 / RJ12 cable to the monitoring unit CAN port and the other end to any CAN input of the smoke sensor. It is possible to connect up to 10 sensors to one CAN port. To do so connect a new RJ11 cable to a free input of an already connected smoke sensor and the other end to the next smoke sensor in a chain. See the picture below. RJ11 or RJ12 cable pinouts can be found in the picture below. After the system will start, configure the CAN bus, after configuration, the LED on the smoke detector will blink dimly once a second.
Now we need to switch TR to position OFF for all sensors except the last sensor. And switch TR to OFF position for the last sensor.
Depending on the version of VT460, please choose the below picture to help you accomplish that.
Case 1 | Older VT460 sensors use a pin head jumper. a) For all sensors except the last sensor in the chain put "pinhead jumper" on pins: 2 and 3. TR is OFF. b) For the last sensor in the chain put "pinhead jumper" on pins: 1 and 2. TR is ON. | |
Case 2 | Newer VT460 sensors use a slide switch. a) For all sensors except the last sensor in the chain switch the slide switch UP to turn up. TR is OFF. b) For the last sensor in the chain switch the slide switch to the BOTTOM/DOWN. TR is ON. |
During system operation, take a needle or paper clip and insert it into the hole on the cover of the sensor, try to move it there until the blinking dimly LED will flash brightly. That means that sensor is in a good state. After inspection, return the sensor /s to a normal state. To do this, either disconnect them from the system, or in a system interface, go to the smoke sensors tab, and restart them.
Avoid high-frequency noise and the impact of dust on the sensor, the noise and dust cause false alarms.
VT460 | |
---|---|
Dimensions | Ø100×45 mm |
Weight | 290 g |
Inputs | 2 x RJ-12 |
Operating temperature | Min. -10° C, Max.80° C |
Operating humidity | Min. 5% - Max. 95% (Non-Condensing) |
Power consumption | 100 mW |
Status Indicators | Red LED |
Max. distance m | 225 m |
HS Code | 8531 10 950 |
Components | Manufactured in E.U. |
Special Features | Daisy chain |
Mounting | On the сeiling |