Product page: https://vutlan.com/can-sensors/27-vt460-smoke-humidity-and-temperature-sensor.html

Physical description

From the picture above:

  1. Temperature & humidity sensor
  2. CAN bus ports
  3. Pinheads (3 pins)
  4. LED (More info in the "LEDs section" in the article: CAN devices connection)


The sensor can not be used on its own. It must be used together with Vutlan monitoring systems.

Installation procedure

Notes on assembly

Installation with the mounting plate provided

The sensor is installed using the mounting plate provided.

Drawings

Connecting sensor

Connect one end of the RJ11 / RJ12 cable to the monitoring unit CAN port and the other end to any CAN input of the smoke sensor. It is possible to connect up to 10 sensors to one CAN port. To do so connect a new RJ11 cable to a free input of an already connected smoke sensor and the other end to the next smoke sensor in a chain. See the picture below. RJ11 or RJ12 cable pinouts can be found in the picture below. After the system will start, configure the CAN bus, after configuration, the LED on the smoke detector will blink dimly once a second. 


Using the pictures below, install a jumper on VT460.

a) For all sensors except the last sensor in the chain put "pinhead jumper" on pins: 2 and 3. TR is OFF.

b) For the last sensor in the chain put "pinhead jumper" on pins: 1 and 2. TR is ON.

Connecting CAN sensors

Testing the smoke sensors

During system operation, take a needle or paper clip and insert it into the hole on the cover of the sensor, try to move it there until the blinking dimly LED will flash brightly. That means that sensor is in a good state. After inspection, return the sensor /s to a normal state. To do this, either disconnect them from the system, or in a system interface, go to the smoke sensors tab, and restart them.

False alarms

Avoid high-frequency noise and the impact of dust on the sensor, the noise and dust cause false alarms.

Technical specifications

VT460
DimensionsØ100×45 mm
Weight290 g
Inputs

2 x RJ-12

Operating temperatureMin. -10° C, Max.80° C
Operating humidityMin. 5% - Max. 95% (Non-Condensing)
Power consumption100 mW
Status IndicatorsRed LED
Max. distance m225 m
HS Code8531 10 950
ComponentsManufactured in E.U.
Special FeaturesDaisy chain
MountingOn the сeiling

Safety instructions

Configuring CAN sensors