Product page: https://vutlan.com/can-sensors/28-vt490-dual-humidity-and-temperature-sensor.html

Function and purpose

High-quality humidity and temperature sensor with reliable price.

...

Communications
Description
Sensor typeCAN digital sensor
Inputs/Outputsx2 RJ11 6P4C ports
Daisy chainYes, the daisy chain is possible for all CAN sensors.
Max. distance from the monitoring unit:225m
LED indicators:Red / Green (RUN/ERR)
Accuracy

T accuracy:±0.4 °C (max), –10 to 85 °C
RH accuracy:± 3% RH (max), 0–80% RH
Resolution0,1 °C
Environmental
Working temperature range:−40 to +100 °С
Humidity operating range:0 to 95% RH
Power Requirement
Power input:12V DC, 1A
Current consumption:1 Watt
Mechanics
Dimensions:68x47x26 mm
Packaging weight:160 g
Mounting options:Desktop, Wall mount
General
Manufactured in:Slovak Republic, European Union
Manufactured by:Vutlan s.r.o.
HS code:9025 11 800
Warranty:90 days

...

1. LEDs: "RUN" (green) - indicates that the appliance is correctly connected to the main module, "ERR" (red) - indicates an error, the appliance lost connection to the main module.

...

Example 1: We have 1 CAN sensor connected to the main module VT8101 on the CAN bus. In this case, this sensor is the only one and the last one in the CAN chain, and its 2nd "TR" switch should be in the "ON" (down) position.

Example 2: We have 5 sensors or modules connected to the main module via the CAN bus. The sensor is not the last sensor in a chain, for example, it is located in the middle of teh the chain. In this case, the "TR" switch must be in the "OFF" (up) position.

...

4. "CAN" - two equivalent digital connectors RJ11 6P4C for the connection to the master module, CAN sensors, or CAN extensions on a CAN bus, with auto-sensing.

...

View file
nameVT490 v14.2 DWGs.pdf
height250

Example connection

Image Added

Connecting CAN devices

Include Page
CAN devices connection
CAN devices connection

...