Reading Elements

The read element request contains the following fields:

...

Sensors in the Vutlan monitoring system

Sensors with a discrete output (clas = discrete)

Possible states: not connected, normal, alarm

Range of possible values: 0, 1

Parameters (attributes):

  • hwport - hardware port (connector name on the device body), read only;
  • reset - Reset the sensor memory or turn off the power:
    • 0 - immediate reset of the sensor alarm;
    • 1..86400 - reset by the timeout, after the specified time;
    • negative value (-1) - auto reset is disabled;
  • high - the upper threshold of the sensor in % (1-200 for airflow, 1-100 for other sensors);
  • low - the lower threshold of the sensor in % (1-200 for airflow, 1-100 for other sensors);
  • reverse - the flag of the sensor output inversion (0 or 1), inverts the sensor state;
  • spec - reference information for sensor adjustment (read only);

If the element does return any one of the attribute from the specified - then the value of this attribute is not determined in the process of work and its installation does not affect the operation of the element.

Elements with a discrete output can also have other attributes.

TypeIconNameAnalog / Built-in / SC408CAN-modules (amount of sensors of this type)Notes
dry
Dry contact
VT16 / Dry contacts board
VT32 / Dry contacts board
VT440 / Dry contacts unit  (16/32/48/64)
VT430 / Rack control unit

door
Access sensorSC530 / Access sensor
VT430 / Rack control unit

airflow
Airflow sensor-

SC450 Aiflow sensor (8)


motion
PIR sensor
VT570 / PIR sensor

VT470 / PIR, vibration and temperature sensor

vibration
Vibration sensorSC541 / Vibration sensor
VT470 / PIR, vibration and temperature sensor

smoke
Smoke sensor
VT560 / Smoke detector
VT460 / Smoke, humidity and temperature sensor



water
Leakage sensor
VT590 / Spot water detector
VT591 / Water leak sensor
-
button
Button--PDUs

Sensors with analog output (clas = analog)

Possible states: not connected, low alarm, low warning, normal, high warning, high alarm

Parameters (attributes):

  • hwport - hardware port (connector name on the device body), read only;
  • vmax - maximum value for the measuring range, read only;
  • vmin - minimum value for the measuring range, read only;
  • low_alarm - the threshold of the "alarm, below normal" state (except for the "factor" type);
  • low_warning - threshold of "warning, below normal" status;
  • high_warning - "warning, above normal" status threshold;
  • high_alarm - threshold of "alarm, above normal" status;
  • at0 is the calibration coefficient in the formula at0*x+at75;
  • at75 is the calibration factor in the formula at0*x+at75;
  • expr - expression for calculating the output value (for conversion sensors);
  • um - the unit of measurement for the value measured by the sensor (if this attribute is missing, the units of measurement are calculated by the type attribute).
  • descr - description of the sensor;

If the element does not return any attribute from the specified - then the value of this attribute is not determined in the process of work and its installation does not affect the operation of the element.

Elements with an analog output can also have other attributes.

TypeIconNameAnalog / Built-in / SC408CAN-modulesNotes
temperature
Temperature sensor
VT500 / Temperature sensor
VT460 / Smoke, humidity and temperature sensor
VT470 / PIR, vibration and temperature sensor
встроенный датчик температуры на материнской плате
humidity
Humidty sensor
VT510 / Humidity sensor
VT460 / Smoke, humidity and temperature sensor
VT430 / Rack control unit

voltage
Voltage sensor
VT520 / AC voltage monitor
-встроенный датчик напряжения на материнской плате
fvoltage
DC voltage monitor
VT410 / DC voltage monitor
-
current
Измерительный датчик тока--распределители питания
fcurrent
Преобразовательный датчик тока
VT420 / Converter 4-20mA
-
vibration
Vibration sensorSC540 vibration sensor-
power
Power sensor--распределители питания
factor
Ratio of the ratio coefficients--распределители питания
frequency
Frequency Sensor--распределители питания

Switches (clas=switch)

Possible states: not connected, on, off, pulse

Type

Icon

Name

Notes

relay
Relay

SC8100 (4)

1-Wire power management,
power management of the analog module and VT408

outlet
Outlet

SC8110 (4)

SC1108 (8)

toggle
Toggle switchSC32xx (АВР)

Devices (clas=devhwr)

Possible states: not connected, normal, alarm

Type

Icon

Name

Notes

reader
iButton reader
ip-cam
IP camera
usb-cam
USB camera
GSM modem
GSM modem

Virtual elements (clas=devirt)

Possible states: not connected, normal, alarm

Feature: created in the system by the user

Type

Icon

Name

Notes

timer
Timer
ping
Ping
logic
Logic scheme
trigger
Trigger
Уведомления 

Notifiers (clas=notifier)

Possible states: normal

Feature: are created in the system by the user, activated by the logic schemes

Type

Icon

Name

Notes

mailer
E-mail notification
snmp trap
Trap PDU
sms
SMS