Function and purpose

Product page: 

Datasheet page:

...

"WLC / Water leak cable" is ordered separately!  When water is in contact with the detection cable resistive sensor indicates the emergence of moisture. The whole area can be effectively monitored by placing the cable near or along with possible flood sources.

Order options

Model

Description

WLC3

WLC / Leak detection cable length is 3m.

Dimensions

...

Usage examples

...

Technical specifications

VT591 / Water leak sensor specifications

Dimensions

60×18×18 mm

Weight

60 g

Input

2 wire (WLC cable)

Detection

Capacitive

Output

RJ11 (6p4c)

Operating temperature

-10 °C to +80 °C

Operating humidity

5% to 95% (Non-Condensing)

Mounting

Mounting bracket included.

Power consumption

60mW

Max. distance m

100 m

HS Code

9025 80 400

Components

Manufactured in E.U.

Special features

Response time: 15 sec., Recovery time: Depends on how fast the sensor dries out

...

WLC / Water leak cable specifications

Description

WLC can work in high humidity, pollution, and hazardous waste

Detectable liquids

Clean, polluted & distilled water; acids; alkalis; alcohols, and other electrically conductive liquid

Diameter

6.5 mm in diameter

Lengths

Order options include 3m, 6m, 10m, 15m, 25m, 50m, or custom length.

Weight

36 g/m

Operating humidity

0% - 95 %

Max. storage temperature

75°C

Max. cable length

100 m

Inputs

x2 wires

Package content

Include Page
VT591 package content
VT591 package content

Connecting WLC / Water leak cable

...

Do not do illustration

Description

Panel
panelIconIdatlassian-warning
panelIcon:warning:
bgColor#FF8F73

The cable can not touch itself. It needs to be straightened.

Panel
panelIconIdatlassian-warning
panelIcon:warning:
bgColor#FF8F73

Do not twist or press down the cable too much. This may lead to deformation. The cable has two sensing wires, these wires can not touch each other.

Panel
panelIconIdatlassian-cross_mark
panelIcon:cross_mark:
bgColor#FF8F73

Do not put the cable on a conductive surface.

Panel
panelIconIdatlassian-cross_mark
panelIcon:cross_mark:
bgColor#FF8F73

You can cut the cable, but you need to isolate the ends so that they do not touch each other. And do not loop the cable.

  1. Connect the "VT591 / Water leak sensor" to the monitoring unit. The connection is plug-an-play.

  2. Connect the terminal cable to the VT591 sensor.

  3. Connect "WLC / Water rope" to terminal cable.

  4. Connect any additional "WLC / Water leak cables" to each other as shown in the picture above to make a chain connection.

  5. Wire the WLC rope around or under potentially leaking objects around the perimeter or under the raised floors.

  6. Put a protective cap on the connector of the last WLC cable in a chain.

  7. The sensor is ready to use.

Analog sensor connection

Include Page
Analog sensors connection
Analog sensors connection

How to test the sensor & sensor cable

  1. Connect the WLC cable to VT591. Connect VT591 to the analog port of the system. The sensor should appear in the Vutlan Web Interface >> “System tree” panel >> “System group” tab >> “Autodetect” sensors. Make sure that the WLC cable is straight or not contacting itself, or any conducting material. The sensor should appear in the system as “Normal” (if the behavior is set to “Normal”), which means that there’s no presence of liquid (the two yellow wires along the WLC cable are not cables shorted).

  2. Take a rag and wet it a little. Touch the rag to both yellow ires on the WLC cable. This should shorten the contact. The VT591 sensor should change the state to “Alarm”.

  3. Dry the cable carefully with a dry cloth.

Installation examples

Please find installation examples in our articles "Water leakage detection using cable sensor and spot sensor" and "Leak detection under raised floors in data centers".

Cable layouts

Cover the whole area

Comprehensive protection for critical areas

Cover the edge area

Prevent leaks from immersing in or spreading out

Covering air-conditioned areas

Key protection against major leakage sources such as alr conditioners

Cable pinouts

The sensor uses a standard Vutlan analog sensor cable(RJ11/RJ12 to RJ11/RJ12) for connecting to the monitoring unit. You can find further instructions at the Analog sensors connection

Technical support

The device does not contain any user-serviceable parts. If the power meter requires service, contact your local sales representative. Do not open the device. Opening the device voids the warranty.

Schematics / Sensitivity adjustment

You can change the R10 resistor using the following schemes.

For example, if your room has very high humidity and the cable is in an alarm state without the spilled liquid being present, you can change R10 to 270k. This should lower the sensitivity level.

...

Troubleshooting

The following table describes potential problems and their possible causes. It also describes checks you can perform or possible solutions for each. After referring to this table, if you cannot resolve the problem, contact your local Vutlan sales representative for assistance.

...