Usually, OSDPv2 is back-compatible with OSDPv1 devices. However, each such device needs to be tested.

...

  1. We recommend connecting no more than x2 devices/readers powering from VT485r. If you power too many devices, a fuse inside the monitoring unit will activate and it will power down the monitoring system.

  2. Terminate B(-) and A(+) end of the line with a 120 Ohm resistor.

  3. VT485r PCB has 120Ohm resistor termination.

  4. Use only twisted pair cables for B(-) and A(+) conductors.

...