Documentation page: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/183471317193421575/VT500VT590+TemperatureLeak+sensor+v2

Product page: https://vutlan.com/analog-sensors/22-vt590-spot-water-detector.html

Function and purpose

For the installation at the bottom of IT racks and cabinets; at the bottom of raised floors; at the bottom of trays and under equipment that can potentially leak. When water is in contact with the both metal cores, the sensor indicates the emergence of moisture.
Attention! Metal cores are detectors of water, mount strictly downwards as close as its possible to a floor.

Technical specifications

...

CommunicationsDescription
Sensor type:Analog sensor
Outputs:x1 RJ11 6P4C port
Daisy chain?No
Max. distance from the monitoring unit:100 m
Environmental
Operating temperature:Min. -10 °C - Max.80 °C

Package includes

Package content can be found at : VT590 package content

Connecting leak sensor

Operating humidity:5 to 95% (Non-Condensing)
Power requirements
Power consumption60mW
Mechanics
Dimensions:60×18×18 mm
Mounting:Mounting bracket included. Installed at the bottom of racks or floors or trays.
Packaging weight:125 g
Cable length:3m
General
Manufactured in:Slovak Republic, European Union
Manufactured by:Vutlan s.r.o.
HS Code:9025 80 400
Warranty:90 days


Package includes

Include Page
VT590 package content
VT590 package content

Drawings

View file
nameVT590_tray_mounting.pdf
height250

View file
nameVT590_leak_sensor.pdf
height250

Connecting the leak sensor

The sensor uses a standard Vutlan analog sensor cable for connecting to the monitoring unitmonitoring unit. You can find further instructions at: Analog sensors connection

...

1) There's a round bump at the bottom of the plastic enclosure of the sensor. It is used for fastening when the sensor is mounted together with the on walls using a screw. In the current example, it is not needed. If you are planning to mount a device defferentlydifferently, do not follow this step.

Cut the round bump using a knife so that the bottom of a plastic enclosure will be flat.

...

    b) Stick a sensor to the mounting bracket following the rule from the next paragraph.


3) If  Depending on the surface where the sensor will be installed follow either A or B. If the surface is conductive, then the electric loop between left and right metal bars sticking out the sensor will be closed, which means there's water which that connects two bars.

A) If the surface is not conductiveconducive. Then mount the sensor metal bars as close to the surface as possible.

B) If the the surface is conductive. Then mount the sensor metal bars a bit further from the surface but not too far, so that the detection of water would be possible.

...

Please find installation examples in our article "Water leakage detection using cable sensor and spot sensor" https://vutlan.

Cable pinouts

Sensor uses com/blog/post/leakage-detection.html.

Image Added

Connecting analog sensors

The sensor uses a standard Vutlan analog sensor cable for connecting to the monitoring unit. You can find further instructions at:

Developer notes:

Include Page
Analog sensors connection

Technical specifications

...

VT590

...

RJ-12 / RJ-11

...

Analog sensors connection

Configure analog sensors

Include Page
Sensor configuration
Sensor configuration

API: managing system elements by 3rd party Software

Vutlan has an open API. Read more at:

https://vutlan.atlassian.net/wiki/spaces/API/pages/335740995/Managing+system+elements