Documentation page: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/183471317193421575/VT500VT590+TemperatureLeak+sensor+v2
Product page: https://vutlan.com/analog-sensors/22-vt590-spot-water-detector.html
Function and purpose
For the installation at the bottom of IT racks and cabinets; at the bottom of raised floors; at the bottom of trays and under equipment that can potentially leak. When water is in contact with the both metal cores, the sensor indicates the emergence of moisture.
Attention! Metal cores are detectors of water, mount strictly downwards as close as its possible to a floor.
Technical specifications
...
Communications | Description |
---|---|
Sensor type: | Analog sensor |
Outputs: | x1 RJ11 6P4C port |
Daisy chain? | No |
Max. distance from the monitoring unit: | 100 m |
Environmental | |
Operating temperature: | Min. -10 °C - Max.80 °C |
Package includes
Package content can be found at : VT590 package content
Connecting leak sensor
Operating humidity: | 5 to 95% (Non-Condensing) |
Power requirements | |
---|---|
Power consumption | 60mW |
Mechanics | |
Dimensions: | 60×18×18 mm |
Mounting: | Mounting bracket included. Installed at the bottom of racks or floors or trays. |
Packaging weight: | 125 g |
Cable length: | 3m |
General | |
Manufactured in: | Slovak Republic, European Union |
Manufactured by: | Vutlan s.r.o. |
HS Code: | 9025 80 400 |
Warranty: | 90 days |
Package includes
Include Page | ||||
---|---|---|---|---|
|
Drawings
View file | ||||
---|---|---|---|---|
|
View file | ||||
---|---|---|---|---|
|
Connecting the leak sensor
The sensor uses a standard Vutlan analog sensor cable for connecting to the monitoring unitmonitoring unit. You can find further instructions at: Analog sensors connection
...
1) There's a round bump at the bottom of the plastic enclosure of the sensor. It is used for fastening when the sensor is mounted together with the on walls using a screw. In the current example, it is not needed. If you are planning to mount a device defferentlydifferently, do not follow this step.
Cut the round bump using a knife so that the bottom of a plastic enclosure will be flat.
...
b) Stick a sensor to the mounting bracket following the rule from the next paragraph.
3) If Depending on the surface where the sensor will be installed follow either A or B. If the surface is conductive, then the electric loop between left and right metal bars sticking out the sensor will be closed, which means there's water which that connects two bars.
A) If the surface is not conductiveconducive. Then mount the sensor metal bars as close to the surface as possible.
B) If the the surface is conductive. Then mount the sensor metal bars a bit further from the surface but not too far, so that the detection of water would be possible.
...
Please find installation examples in our article "Water leakage detection using cable sensor and spot sensor" https://vutlan.
Cable pinouts
Sensor uses com/blog/post/leakage-detection.html.
Connecting analog sensors
The sensor uses a standard Vutlan analog sensor cable for connecting to the monitoring unit. You can find further instructions at:
Developer notes:
Include Page | ||
---|---|---|
|
Technical specifications
...
VT590
...
RJ-12 / RJ-11
...
|
Configure analog sensors
Include Page | ||||
---|---|---|---|---|
|
API: managing system elements by 3rd party Software
Vutlan has an open API. Read more at:
https://vutlan.atlassian.net/wiki/spaces/API/pages/335740995/Managing+system+elements